AEMC 3711

AEMC Model 3711 Clamp-Ìwé Àfọwọ́kọ Olùlò Olùdánwò Ìdènà Lórí Ilẹ̀

Awoṣe: 3711

Ọrọ Iṣaaju

The AEMC Model 3711 is a portable clamp-on ground resistance tester designed for measuring electrical ground rod and grid resistance in multi-grounded systems. This instrument offers a non-intrusive method for testing without the need for auxiliary rods or disconnecting the ground system. It also measures leakage, neutral, and phase currents, providing a comprehensive solution for electrical system analysis.

Alaye Aabo

IKILO: Always read and understand all safety instructions before operating this instrument. Failure to do so may result in serious injury or death.

  • This instrument is rated CAT III, indicating its suitability for measurements in building installations.
  • Adhere to all local and national safety codes and regulations.
  • Má ṣe lo ohun èlò náà tí ó bá dàbí ẹni pé ó ti bàjẹ́ tàbí tí ó ń ṣiṣẹ́ lọ́nà tí kò dára.
  • Ensure the battery compartment is securely closed before use.
  • Avoid contact with live circuits during measurement.
  • The instrument is double-insulated for enhanced safety.

Ohun ti o wa ninu Apoti

Rii daju pe gbogbo awọn nkan wa lori ṣiṣi silẹ:

  • AEMC Ground Resistance Tester Model 3711
  • Calibration Check Loop, 25Ω
  • Ọran Gbigbe Lile
  • Batiri Batiri 9V
  • Afowoyi Olumulo (iwe-ipamọ yii)

Ọja Pariview

AEMC Model 3711 Clamp-On Ground Resistance Tester showing a reading of 9.8 Ohms on its display.

Image: The AEMC Model 3711 Clamp-On Ground Resistance Tester. This image displays the device with its red clamp jaws open, a black body, and a green digital display showing "9.8 Ω". Control buttons are visible below the display.

The AEMC Model 3711 features an ergonomic design for one-handed operation. Its robust polycarbonate construction ensures durability for outdoor use. Key components include:

  • Clamp Ẹnu: 1.25" opening to accommodate ground rods and cables up to 1000kcmil.
  • Ifihan LCD: Digital readout for resistance and current measurements.
  • Awọn bọtini Iṣakoso: For power, data hold, and mode selection.
  • Abala Batiri: Located at the rear for a 9V battery.

Eto ati Batiri sori

  1. Open the battery compartment cover on the rear of the instrument.
  2. Insert the supplied 9V Alkaline battery, observing correct polarity.
  3. Pa ideri batiri naa ni aabo.
  4. Press the "ON" button to power on the device. The display should illuminate.

Awọn ilana Iṣiṣẹ

Ground Resistance Measurement

  1. Power on the AEMC 3711.
  2. Ṣii clamp jaws by pressing the release lever.
  3. Gbe awọn clamp around the ground conductor or rod to be tested, ensuring the jaws are fully closed.
  4. The instrument will automatically measure and display the ground resistance in Ohms (Ω).
  5. For stable readings, allow approximately one second for the measurement to settle.
  6. To hold the current reading on the display, press the "HOLD" button. Press again to release.

Iwọn Iwọn lọwọlọwọ

  1. Power on the AEMC 3711.
  2. Ṣii clamp ẹrẹkẹ.
  3. Gbe awọn clamp around the conductor carrying the current to be measured (leakage, neutral, or phase current). Ensure the jaws are fully closed.
  4. The instrument will automatically measure and display the current in Amperes (A) tabi milliAmpere (mA).
  5. The current measurement function provides direct readings for leakage current flowing to ground or circulating in ground loops (down to 1mA) and neutral/phase currents (up to 30A RMS).

Itọju ati odiwọn

Ninu

Nu irinse naa pẹlu asọ, damp asọ. Ma ṣe lo abrasive ose tabi epo.

Batiri Rirọpo

When the low battery indicator appears on the display, replace the 9V battery as described in the "Setup and Battery Installation" section.

Ṣayẹwo odiwọn

Use the supplied 25Ω calibration check loop to verify the instrument's accuracy periodically. Clamp the tester around the loop; the reading should be approximately 25Ω. If the reading deviates significantly, contact AEMC customer support for service.

Ibi ipamọ

Store the instrument in its hard carrying case in a dry, cool environment when not in use. Remove the battery if storing for extended periods.

Laasigbotitusita

  • No Display/Instrument Not Powering On: Ṣàyẹ̀wò bí batiri ṣe ń ṣiṣẹ́ kí o sì rí i dájú pé batiri náà ní agbára tó. Rọ́pò rẹ̀ tí ó bá pọndandan.
  • Awọn kika aiduroṣinṣin: Rii daju pe clamp jaws are fully closed around the conductor. Verify there is no excessive electrical noise in the environment.
  • Àmì "OL" tàbí Àpọ̀jù Ẹ̀rù: The measured value exceeds the instrument's range. Ensure the correct measurement function is selected or the circuit parameters are within the device's limits.
  • Awọn kika ti ko pe: Perform a calibration check using the 25Ω loop. If the issue persists, contact technical support.

Awọn pato

ParamitaIye
Ground Resistance RangeAutoranging 0.01 to 1200Ω
Iwọn Iwọn Iwọn lọwọlọwọAutoranging 1mA to 30.00A RMS
Resistance Measuring Frequency2403Hz
Current Measuring Frequency47 si 800Hz
Accuracy (Resistance)±2% reading ±0.02Ω (up to 25% of reading for 600-1200Ω)
Awọn iwọn otutu ti nṣiṣẹ-10 si 55°C (14 si 131°F)
Orisun agbaraBatiri 9V (pẹlu)
Iwọn1kg (2.2lbs)
Awọn iwọn (H x W x D)235 x 100 x 55mm (9.25 x 3.94 x 2.17 inches)
Ibẹrẹ ẹnu1.25 inches
Awọn idiyele AilewuEN 61010, CAT III, UL approved, CE marked

Atilẹyin ọja ati Support

For warranty information, technical support, or service inquiries, please refer to the official AEMC Instruments webojula tabi kan si wọn onibara iṣẹ Eka. Tọju iwe-ẹri rira rẹ fun awọn ẹtọ atilẹyin ọja.

© AEMC Instruments. All rights reserved.

Afowoyi yii le yipada laisi akiyesi.

Ask a question about this manual