SoliTek SOLID Series Solar Modules

Awọn ilana Lilo
- Read this guide entirely before installation.
- This document provides minimum requirements and recommendations for safe and successful installation of SoliTek PV modules and is necessary to retain compliance with IEC 61215, IEC 61730, and UL 61730 standards.
- This guide provides basic information on JSC SoliTek Cells SOLID series photovoltaic modules, including their installation and safe handling.
- All instructions should be read and understood before attempting installation. Contact your dealer or JSC SoliTek Cells for further information if needed.
- This documentation refers to the PV modules themselves and is not a comprehensive installation manual for personnel not specifically trained in PV modules.
- It serves as a general but strictly mandatory reference for the installer. Infringement or inaccurate observance of any clause in this documentation voids the warranty.
- The installer must understand and follow all applicable local, state, and federal regulations and standards for building construction, electrical design, fire, and safety.
- Check with local authorities for permitting requirements before installing or maintaining PV modules, and become familiar with mechanical and electrical requirements for photovoltaic systems.
- Ikuna lati tẹle awọn itọnisọna ninu itọsọna yii le ba awọn paati eto jẹ, ṣe eewu eewu, ba ohun-ini jẹ, tabi sọ atilẹyin ọja di asan.
- Rooftop PV systems should only be installed on dwellings formally analyzed for structural integrity and confirmed to be capable of handling the additional weighted load of PV system components (including PV modules) by a certified building specialist or engineer.
Awọn ibeere gbogbogbo
- Jọwọ ka itọsọna yii patapata ṣaaju fifi sori ẹrọ.
- Idi ti iwe yii ni lati pese awọn ibeere ti o kere ju ati awọn iṣeduro fun ailewu ati fifi sori aṣeyọri ti awọn modulu SoliTek PV.
- Iwe yii tun ni awọn ibeere pataki lati ṣe idaduro ibamu module SoliTek PV pẹlu IEC 61215, IEC 61730, UL 61730.
- Itọsọna yii ni alaye ipilẹ ninu JSC “Awọn sẹẹli SoliTek” SOLID jara awọn modulu fọtovoltaic, fifi sori wọn ati mimu ailewu mu. Gbogbo awọn ilana yẹ ki o ka ati loye ṣaaju igbiyanju fifi sori ẹrọ. Ti awọn ibeere eyikeyi ba wa, jọwọ kan si alagbata rẹ tabi JSC “Awọn sẹẹli SoliTek” fun alaye siwaju sii.
- This documentation refers to the PV-modules themselves and is not meant to be a complete installation manual for personnel not specifically trained to PV-modules.
- It serves as a general but strictly mandatory reference for the Installer.
- Irufin tabi akiyesi aipe ti eyikeyi gbolohun ọrọ ti iwe-aṣẹ yi sọ atilẹyin ọja di ofo.
- Olupilẹṣẹ gbọdọ ni oye ati tẹle gbogbo awọn ilana agbegbe, ipinle, ati Federal ti o wulo ati awọn iṣedede fun ikole ile, apẹrẹ itanna, ina, ati ailewu, ati pe o gbọdọ ṣayẹwo pẹlu awọn alaṣẹ agbegbe lati pinnu awọn ibeere iyọọda to wulo ṣaaju igbiyanju lati fi sori ẹrọ tabi ṣetọju awọn modulu PV ati pe o yẹ di faramọ pẹlu ẹrọ ati awọn ibeere itanna fun awọn ọna ṣiṣe fọtovoltaic.
- Ikuna awọn ilana itọsona ninu itọsọna yii le ba awọn paati eto jẹ, awọn oṣiṣẹ lewu, ba ohun-ini jẹ, tabi sọ atilẹyin ọja di asan.
- Awọn ọna PV Rooftop yẹ ki o fi sori ẹrọ nikan lori awọn ibugbe ti o ti ṣe atupale ni deede fun iduroṣinṣin igbekalẹ ati timo lati ni agbara lati mu ẹru iwuwo afikun ti awọn paati eto PV, pẹlu awọn modulu PV, nipasẹ alamọja ile ti a fọwọsi tabi ẹlẹrọ.
- For your safety, do not attempt to work on a rooftop until safety precautions have been identified and taken, including, without limitation fall protection measures, ladders or stairways, and personal protective equipment (PPE).
- For your safety, do not install or handle PV modules under adverse conditions, including, without limitation strong or gusty winds, and wet or frosted roof surfaces.
- Itumọ module PV alapin-alapin ni apejọ ti a ti laminated ti awọn sẹẹli oorun ti a fi sinu ohun elo idabobo laarin awọn iwe gilasi meji.
- Tọju iwe-ipamọ yii ni aaye ailewu fun itọkasi ọjọ iwaju.
- Maṣe gbiyanju lati ṣajọpọ module naa, ati pe ma ṣe yọkuro eyikeyi awọn ami orukọ ti a so tabi awọn paati! Ṣiṣe bẹ yoo sọ atilẹyin ọja di ofo.
Mimu & Ohun elo
Imudani
- SoliTek PV modules must be transported in the supplied packaging only and kept in the packaging until they are ready to be installed.
- Protect pallets against movement and exposure to damage during transportation. Secure pallets from falling over.
- Maṣe kọja giga ti o pọju ti awọn palleti lati wa ni tolera, bi itọkasi lori apoti pallet.
- Store pallets in a cool and dry location until the PV modules are ready to be unpackaged.
- SoliTek PV modules are heavy and should be handled with care. Never use the junction box or cables as a grip.
- Do not exert mechanical stress on the cables.
- Never step on PV modules or drop or place heavy objects on them.
- Be careful when placing PV modules on hard surfaces and secure them from falling.
- Broken glass can result in personal injury. PV modules with broken glass cannot be repaired and must not be used.
- Broken or damaged PV modules must be handled carefully and disposed of properly.
ÌWÉ
Awọn ihamọ
- SoliTek PV modules must be mounted on appropriate mounting structures positioned on suitable buildings, the ground, or other structures suitable for PV modules (e.g. carports, building facades or PV trackers).
- PV modules must not be mounted on moving vehicles of any kind. Modules must not be installed in locations where they could be submerged in water.
- Do not install modules above 2000 m (6561 ft) altitude above sea level
- Ina ogidi lainidii ko gbọdọ ṣe itọsọna lori awọn modulu SoliTek PV.
Awọn iṣeduro
- SoliTek ṣeduro pe ki a gbe awọn modulu PV sori igun titẹ ti o kere ju ti awọn iwọn 10 lati gba laaye fun mimọ ara ẹni to dara lati ojo.
- Apa kan tabi iboji pipe ti module PV tabi awọn modulu le dinku iṣẹ ṣiṣe eto ni pataki.
- SoliTek ṣe iṣeduro idinku iye iboji jakejado ọdun lati mu iye agbara ti a ṣe nipasẹ awọn modulu PV.
- Ga eto voltages could be induced in the event of an indirect lightning strike, which could cause damage to PV system components.
- The open area of wire loops should be minimized in order to reduce the risk of lightning-induced voltage gbooro.
- Fentilesonu module ti o dara julọ ati awọn kebulu asopọ kukuru pọ si iṣelọpọ agbara itanna.
Fun awọn modulu bifacial:
- O ti wa ni niyanju lati mu PV iga nronu lati ilẹ ki ina diẹ le ajo nisalẹ awọn module ati ki o si fi irisi
- Ere bifacial pọ si ni pataki ti awọn modulu ba fi sori ẹrọ loke funfun (iye albedo giga), awọn roboto ti o tan imọlẹ.
Itanna fifi sori
AABO
- PV modulu le gbe awọn ti isiyi ati voltage nigba ti fara si ina ti eyikeyi kikankikan. Itanna lọwọlọwọ posi pẹlu ga ina kikankikan. DC voltage ti 50 Volts tabi ga julọ jẹ apaniyan. Kikan si awọn iyika laaye ti eto PV ti n ṣiṣẹ labẹ ina le ja si mọnamọna apaniyan.
- De-agbara awọn modulu PV nipa yiyọ wọn kuro patapata lati ina tabi nipa bo oju iwaju wọn pẹlu ohun elo akomo. Nipa awọn ilana aabo fun ohun elo itanna laaye nigbati o n ṣiṣẹ pẹlu awọn modulu ti o farahan si eyikeyi ina. Lo awọn irinṣẹ idayatọ ati maṣe wọ awọn ohun-ọṣọ ti fadaka lakoko ti o n ṣiṣẹ pẹlu awọn modulu PV.
- Lati yago fun arcing ati mọnamọna itanna, ma ṣe ge asopọ itanna labẹ fifuye. Awọn asopọ ti ko tọ le tun ja si arcing ati mọnamọna itanna. Jeki awọn asopọ ti o gbẹ ati mimọ ati rii daju pe wọn wa ni ipo iṣẹ to dara. Maṣe fi awọn nkan ti fadaka sinu awọn asopọ tabi yi wọn pada ni ọna eyikeyi lati le ni aabo asopọ itanna kan.
- Do not touch or handle PV modules with broken glass unless the PV modules are first disconnected, and you are wearing proper PPE. Avoid handling PV modules when they are wet unless cleaning the PV modules as directed in this manual. Never touch electrical and wet connections without protecting yourself with insulated gloves.
- The modules are qualified for Class II protection against electrical shock, in accordance with clause 4 of IEC 61730-1:2016, which can be used in systems operating at > 50 V DC or >240 W, where general contact access is anticipated and modules qualified for safety through UL 61730 within this application class are considered to meet the requirements of Safety Class II.
- Fifi sori awọn ọna ṣiṣe fọtovoltaic oorun nilo awọn ọgbọn amọja ati imọ. O yẹ ki o ṣe nipasẹ oṣiṣẹ ti o pe ati ti o ni imọran pataki. Awọn insitola dawọle gbogbo ewu ti ipalara, pẹlu ewu ti ina-mọnamọna.
- Lo ohun elo nikan, awọn asopọ, onirin ati ohun elo iṣagbesori ti a ṣe apẹrẹ pataki fun lilo ninu eto fọtovoltaic kan.
- Before any manipulation at an installed PV plant, switch it off first on the AC-side, and then on the DC side of the inverter or the charge controller.
- Nigbati gige asopọ awọn onirin ti a ti sopọ si module fọtovoltaic ti o farahan si ina, arc ina le waye. Arcs le fa ina, bẹrẹ ina, tabi bibẹẹkọ ṣẹda awọn iṣoro ailewu (ti o to ipaya ina apaniyan).
- Ṣayẹwo fun ku voltage before starting and observe the local safety-relevant regulations for such working conditions.
- Labẹ awọn ipo deede, module fọtovoltaic le gbejade lọwọlọwọ diẹ sii ati/tabi voltage (nibi: 30V DC) ju royin ni boṣewa igbeyewo ipo.
- Kan si pẹlu DC voltage ti 30 V tabi diẹ ẹ sii jẹ eewu. Ṣọra nigba lilo onirin tabi mimu awọn modulu ti o farahan si imọlẹ oorun.
- Nikan so awọn module pẹlu awọn kanna won won o wu lọwọlọwọ ni jara. Ti o ba ti modulu ti wa ni ti sopọ ni jara, lapapọ voltage jẹ dogba si awọn apao ti awọn ẹni kọọkan module voltages.
- Nikan so modulu tabi jara awọn akojọpọ ti awọn module pẹlu kanna voltage in parallel. If modules are connected in parallel, the total current is equal to the sum of the individual module or series combination currents.
- Nigbagbogbo lo iru module kanna laarin eto fọtovoltaic kan pato.
- If the sum of short circuit currents of the parallel-connected modules exceeds the reverse current, string diodes or fuses have to be used in each string of modules connected in parallel. These string diodes or fuses have to be qualified for the maximum expected current and voltage. The fuse rating value is also corresponds to the maximum reverse current that a module can withstand. The reverse current value can be found on the product label, in the product datasheet or in chapter 8 of the installation manual. Observe the instructions and safety precautions for all other components used in the system, including wiring and cables, connectors, DC-breakers, inverters, etc.
- Lo awọn ohun elo aabo ti o yẹ (awọn irinṣẹ ti o ya sọtọ, awọn ibọwọ dielectric, bata ati bẹbẹ lọ) ti a fọwọsi fun lilo lori awọn fifi sori ẹrọ itanna.
Iṣeto ni
- Labẹ awọn ipo deede, module fọtovoltaic le ni iriri awọn ipo ti o gbejade lọwọlọwọ diẹ sii ati/tabi voltage than reported at Standard Test Conditions (STC: 1000 W/ m2, AM 1.5, and 250C/770F cell temperature) or Bifacial nominal power index(BNPl front irradiance 1000 W/m2, back irradiance 135 W/m2 AM 1.5, and 25 OC/770F cell temperature). The short-circuit current (ISC) should be multiplied by a factor of 1.25 and the open-circuit voltage (VOC) yẹ ki o jẹ isodipupo nipasẹ ipin kan ti o to 1.25 da lori iwọn otutu ibaramu ti o kere julọ ati ti o ga julọ ti o gbasilẹ fun ipo fifi sori ẹrọ nigbati o ba pinnu paati voltage-wonsi, adaorin ti isiyi-wonsi, fiusi titobi, ati iwọn ti awọn idari ti a ti sopọ si PV o wu.
- Voltages jẹ aropọ nigbati awọn modulu PV ti sopọ taara ni jara, ati awọn ṣiṣan module jẹ aropọ nigbati awọn modulu PV ti sopọ taara ni afiwe. Awọn modulu PV pẹlu awọn abuda itanna oriṣiriṣi ko gbọdọ sopọ taara ni jara. Lilo awọn ẹrọ itanna ẹni-kẹta ti o dara ti o sopọ si awọn modulu PV le mu awọn asopọ itanna oriṣiriṣi ṣiṣẹ ati pe o gbọdọ fi sii ni ibamu si awọn itọnisọna pato ti olupese.
- Iwọn to pọ julọtage of serial interconnection of the modules must be less than the maximum certified module’s system voltage. Bakannaa, awọn ti o pọju input voltage ti awọn ẹrọ oluyipada ati ti awọn miiran itanna awọn ẹrọ ni awọn eto gbọdọ wa ni ya sinu iroyin. Awọn ìmọ Circuit voltage of the array string needs to be calculated at the lowest expected a mbient temperature forthe location. The maximal system voltage for the module is indicated in the module’s datasheet.
- Accordingly, for BLACKSTAR, SOLID or MAGNUS series modules, the values of ISC and VOC under STC or BNPI marked on this module should be multiplied by a factor of 1,25 when determining component voltage ratings, conductor current ratings, fuse sizes, and size of controls connected to the PV output. In the USA, referto Section 690-8 of the National Electrical Code (N EC) for an additional multiplying factor of 125 percent (80 percent de-rating) which may be applicable.
ẸRỌ IDAABOBO LORI lọwọlọwọ (OCPD)
- When the potential reverse current of a PV string exceeds the rated SoliTek PV module series fuse rating (values indicated at the module datasheet) an overcurrent protection device (OCPD) must be used.
- An overcurrent protection device is required for each series string if more than two series are connected in parallel.
- In this case, it is needed to use one fuse per string rated at 1.25 x Isc or higher (Isc is the PV module’s short circuit current at STC). A PV fuse on each PV string will protect the PV modules and conductors from overcurrent faults and help minimize any safety hazards.
- The PV fuse will also isolate the faulted PV string so the balance of the PV system can continue to generate electricity.
- Fiusi amp rating ≥ 1.25 x Isc
- Yan igbelewọn boṣewa ti o ga julọ ni katalogi ti awọn Fuses PV to wa.
- Isc = Kukuru-yipo lọwọlọwọ ti module kan ni Standard Igbeyewo Awọn ipo (STC).
- Ṣiyesi awọn iye ti Isc ti awọn modulu SoliTek, iye ti o tọ ti PV Fuses lati ṣee lo ni fifi sori ẹrọ jẹ 30 A. SoliTek ṣe iṣeduro lilo awọn fiusi PV ni mejeeji awọn oludari rere ati odi.
CABLE & WIRING
Awọn modulu SoliTek PV ni a pese pẹlu boṣewa meji, awọn kebulu iṣelọpọ ti oorun ti o pari pẹlu awọn asopọ PV ti o ṣetan fun awọn fifi sori ẹrọ pupọ julọ. Ebute rere (+) ni asopọ akọ nigba ti ebute odi (-) ni asopọ abo. Asopọmọra module jẹ ipinnu fun awọn ọna asopọ lẹsẹsẹ (ie, akọ (+) si obinrin (-) awọn asopọ interconnections) ṣugbọn tun le ṣee lo lati so awọn ẹrọ itanna ẹni-kẹta ti o dara ti o le ni awọn atunto onirin omiiran niwọn igba ti awọn ilana olupese ba tẹle.
Lo wiwọ aaye pẹlu awọn agbegbe abala-agbelebu ti o yẹ ti o jẹ ifọwọsi fun lilo ni lọwọlọwọ kukuru kukuru ti module PV. Gbogbo onirin gbọdọ jẹ idayatọ meji, awọn kebulu ti o ni asopọ agbelebu pẹlu iwọn to kere ju ti 1,8 kV (ju 1500 V vol.tage) ati iwọn otutu ti o kere ju ti 90 ˚C (190 °F). Iwọn waya ko kere ju 4 mm² (12 AWG). Iru idabobo yẹ ki o yẹ fun iru ọna fifi sori ẹrọ ti a lo ati pe o gbọdọ pade IEC 61730 ati awọn ibeere Kilasi Aabo II.
- Ipele idabobo: 1,8 kV (adaorin-adaorin).
- Iwọn otutu: -40°C titi de +90°C (-40°F titi de 190°F) o kere ju.
- Ikole ti adaorin: Tinned ti idaamu Ejò okun waya pẹlu Ejò ti nw tobi ju 99,9%.
- Idabobo akọkọ: polyethylene ti o ni asopọ agbelebu (XLPE), imole oorun ati ọrinrin sooro, idaduro ina. Dara fun conduit ati raceways fi sori ẹrọ si ipamo.
- Idabobo (jaketi): thermoplastic, sooro ina orun, ina retardant, omi sooro.
- Iwọn ila opin okun ti o kere ju pẹlu idabobo – 5,2 mm (2,05 inch).
- Abala agbelebu ti o kere ju - 4 mm² (12 AWG).
SoliTek ṣeduro awọn fifi sori ẹrọ lati lo awọn kebulu ti o ni aabo oorun nikan ti o yẹ fun wiwi lọwọlọwọ (DC) ni awọn eto PV. Awọn kebulu yẹ ki o wa titi si eto iṣagbesori ni ọna ti a yago fun ibajẹ ẹrọ ti okun ati / tabi module naa. Ma ṣe kan wahala si awọn kebulu. Fun atunṣe, lo awọn ọna ti o yẹ, gẹgẹbi awọn asopọ okun ti ina-sooro ati/tabi awọn agekuru iṣakoso waya. Lakoko ti awọn kebulu naa jẹ sooro oorun ati mabomire, nibiti o ti ṣee ṣe, yago fun ifihan oorun taara ati ibọmi omi ti awọn kebulu naa.
Standard ipari ti awọn kebulu lati awọn apoti ipade jẹ 1,2 m (47,24 inch). O ti pinnu pe awọn panẹli meji yoo sopọ laarin eto naa.
OGUN
- Module grounding must be done in accordance with the electrical design and construction specifications, procedures, regulations and other special grounding requirements applicable to the installation sites. If grounding is needed, it should be done accordingly:
Framed type modules grounding
Awọn ihò ti a samisi pẹlu aami ilẹ-ilẹ lori fireemu le ṣee lo fun ilẹ nikan. Maṣe lu awọn ihò ilẹ-ilẹ afikun lori fireemu module.
The grounding conductor or strap may be copper, copper alloy, or any other material acceptable foruse as an electrical conductor in accordance with local electric codes and regulations.
Adaorin ilẹ gbọdọ lẹhinna ṣe asopọ si ilẹ nipa lilo elekiturodu ilẹ ti o dara.
A bolted connection is required; it incorporates:
- Iwọn boluti ti M4.
- Ifoso ehin labẹ ori boluti tabi boluti serrated gbọdọ wọ inu awọn aṣọ aibikita bi fireemu anodized.
- A fasten nut o dara fun M4 boluti.
- Gbogbo ohun elo yoo jẹ ti irin ti ko ni irin, irin alagbara irin-ila 300, tabi aabo ipata ti o yẹ.
- Yiyi ti a ṣe iṣeduro ti tiipa nut jẹ 2 Nm÷2.2 Nm (1,48÷1,62 ft-lb).
- Boluti ilẹ ni lati lọ nipasẹ gbogbo awọn eroja asopọ.

- Awọn ẹrọ ti a ṣe akojọ ati idamọ fun sisọ awọn fireemu onirin ilẹ ti awọn modulu PV ni idasilẹ lati ilẹ awọn fireemu ti fadaka ti o farahan ti module si awọn ẹya fifi sori ilẹ.
- In any case the grounding screws or other parts have to be used separately from the mounting parts of the module.
- Alternate grounding options built through the mounting system are acceptable as long as they have been IEC and UL approved.
- Grounding resistance of the grounding structure shall be reached according to local regulations, Eurocodes, or other legal normative references.
Frameless type modules grounding
- Due to that modules are without frame, grounding is not forseen. Other PV plant equipment should be grounded according to the local and national electrical codes.
AWỌN ỌRỌ
- Connectors for SoliTek PV panels are Stäubli MC4-Evo 2. Keep connectors dry and clean and ensure that connector caps are hand-tight before connecting the modules.
- Ma ṣe gbiyanju ṣiṣe asopọ itanna pẹlu tutu, idoti, tabi bibẹẹkọ awọn asopọ ti ko tọ.
- Yago fun ifihan ina orun ati ibọmi omi ti awọn asopọ. Yago fun awọn asopọ ti o sinmi lori ilẹ tabi dada orule.
- Do not disconnect under load. Faulty connections can result in arcs and electrical shock.
- Ṣayẹwo pe gbogbo awọn asopọ itanna ti wa ni ṣinṣin ni aabo. Rii daju pe gbogbo awọn asopọ titiipa ti ṣiṣẹ ni kikun ati titiipa.
BYPASS DIODS
The PV module’s junction box contains 3 bypass diodes (one in each part of split junction box; Schottky type) connected in parallel with the PV cell strings. In the case of partial shading (hot-spot effect), the diodes bypass the current generated by the non-shaded cells, therebylimiting module heating and performance losses.
Awọn diodes fori kii ṣe awọn ẹrọ aabo lọwọlọwọ. Awọn diodes fori dari lọwọlọwọ lati awọn okun sẹẹli ni iṣẹlẹ ti iboji apa kan. Awọn abuda ti awọn diodes wọnyi:
- Voltage Rating – 50V.
- Iwọn lọwọlọwọ - 25 A.
FIRE kilasi Rating
- SoliTek SOLID Bifacial ati Blackstar module ti ni ifọwọsi nipasẹ idanwo ina IEC ati aṣeyọri Flammability Class A. Ayẹwo ina ni a ṣe ni itara ti 127 mm (5 inch) fun 300 mm (11,81 inch), bi a ti paṣẹ ni aaye A.2.5 ti IEC 61730-2.
- SoliTek SOLID Bifacial has fire rating of 28 according to UL1703-2 standard. SoliTek Blackstar has fire rating of 29 according to UL1703-2 standard.
Iṣisẹ ẹrọ
- The mechanical loads described in this manual are the test loads.
- For calculating the equivalent maximum design loads, a safety factor of 1.5 (Design load×1.5 safety factor=Mechanical test load) needs to be considered in compliance with the requirements of the local laws and regulations.
Awọn ibeere gbogbogbo
- Modules can be mounted in landscape or portrait orientation. For the bifacial modules, in order to get notable bifacial gain, the distance between the bottom of the modules and the roof or ground surface shall be at least 0,8 m (31,50 inch).
- Also, the bifacial gain increases significantly if modules are installed above white, light-reflecting surfaces (under surfaces with high albedo value).
- If the mounting rails are installed across the module, the bifaciality effect will be lower due to back-side cells shading.
- Jọwọ ṣe akiyesi awọn ilana aabo ati awọn ilana fifi sori ẹrọ ti o wa pẹlu eto iṣagbesori. Ti o ba jẹ dandan, jọwọ kan si olupese taara fun alaye siwaju sii.
- The modules must be safely set onto the mounting rail.
- The whole rail supporting the photovoltaic system must be strong enough to resist potential mechanical pressures caused either by wind or snow, in accordance with local, regional and state safety (and other associated) standards.
- The mounting system shall be tested and inspected by a third-party testing institution with static mechanical analysis capacity in accordance with local national standards or international standards.
- Before installing modules on a roof, ensure that the roof construction is suitable.
- In addition, any roof penetration required to mount the modules must be properly sealed to prevent leaks.
- Rii daju wipe awọn iṣagbesori iṣinipopada yoo ko deform tabi ni ipa lori awọn module nigba ti o gbooro bi kan abajade ti gbona imugboroosi.
- The module can appear thermal expansion and cold contraction; thus, the interval between two adjoining modules shall be no lesser than 10 mm (0,39 inch).
- Ma ṣe gbiyanju lati lu awọn iho ni dada gilasi ati awọn fireemu ti awọn modulu nitori eyi yoo sọ atilẹyin ọja di ofo.
- The mounting method must not result in the direct contact of dissimilar metals with the aluminum frame of the modules that will result in galvanic corrosion.
Awọn ohun elo iṣagbesori gbọdọ jẹ ti awọn ohun elo ti o tọ, anti-corrosive ati awọn ohun elo UV (irin irin alagbara ati awọn ohun elo aluminiomu anodized ni a ṣe iṣeduro).
Iṣagbesori pẹlu CLAMPS
- Lo o kere ju 4 laminate clamps lati fix awọn module lori iṣagbesori afowodimu. Awọn modulu clamps irin awọn ẹya ko yẹ ki o wa sinu olubasọrọ pẹlu iwaju tabi pada gilasi. Nigbati o ba yan iru clamp-iṣagbesori ọna, lo ni o kere mẹrin clamps lori kọọkan module; meji clamps yẹ ki o wa ni so lori kọọkan gun ẹgbẹ. Da lori agbegbe afẹfẹ ati egbon èyà, afikun clamps le nilo lati rii daju wipe awọn module le ru awọn fifuye.
- Clamps tightening iyipo yẹ ki o wa ni o kere 15 Nm (11,06 ft-lb), sugbon ko tobi ju 20 Nm (14,75 ft-lb). Nigbagbogbo, 15 Nm (11,06 ft-lb), ti de ọdọ nigbati pro aluminiomu mejifiles ọwọ kọọkan miiran. Nigbati module kan ti fi sori ẹrọ ni iṣalaye aworan lori oke ile ti o ni> 45° ite, afikun kio ni isalẹ module naa nilo.

SOLID Black, Semi-clear, Satin, Agro Frameless
Pẹlu awọn afowodimu transversal


BLACKSTAR, SOLID Black 35(40) mm, SOLID Semi-clear 35(40) mm, SOLID Satin 35(40) mm, SOLID Agro 35(40) mm, Magnus Framed mounting
- Nigbati o ba yan iru clamp-iṣagbesori ọna, lo ni o kere mẹrin clamps lori kọọkan module; meji clamps yẹ ki o wa ni so lori kọọkan ẹgbẹ ti awọn module. Awọn modulu clamps ko yẹ ki o wa sinu olubasọrọ pẹlu awọn iwaju gilasi ati ki o ko gbodo deform awọn fireemu.
- Rii daju lati yago fun awọn ipa ojiji lori awọn sẹẹli oorun lati module clamps.
- The module frame is not to be modified under any circumstances. Do not to block the drain hole of the frame.
- Awọn ipari ti clamp should be at least 30 mm (1,18 inch).
- Awọn clamp gbọdọ ni lqkan fireemu module nipa o kere 5 mm (0,2 inch), sugbon ko siwaju sii ju 10mm (0,4 inch).
Pẹlu awọn afowodimu transversal

Laisi awọn afowodimu transversal tabi awọn afowodimu jẹ papẹndikula si fireemu ẹgbẹ gigun

Pẹlu eto ifibọ

Iṣagbesori pẹlu boluti
- Awọn module gbọdọ wa ni so ati ki o ni atilẹyin nipasẹ mẹrin M8 alagbara, irin boluti nipasẹ awọn itọkasi iṣagbesori ihò lori transversal ifi. Torque lori clamp bolt has to be in range of 8÷10 Nm (5,9÷7,38 ft-lb). The transversal bars positioning is shown in Figure 3.
- If additional mounting points are required, depending on the local wind and snow loads, then a mounting solution with clamphardware ni lati yan.

- Mounting with bolts can be done only through dedicated predrilled holes in the frame.
- Liluho titun iho ti wa ni ewọ ati ki o yoo atilẹyin ọja di ofo.

IPO TI BOX JUNCTION
- Fun aaye laarin apoti ipade ati eti module tabi awọn iwọn miiran ti ipo apoti ipade ati awọn agbegbe jọwọ tọka si awọn isiro ti o han ni isalẹ.

ITOJU
- Lati rii daju iṣẹ ṣiṣe module ti o dara julọ, SoliTek ṣeduro atẹle naa:
- Ti o ba jẹ dandan, gilasi iwaju ti module naa le di mimọ pẹlu omi ati kanrinkan rirọ tabi asọ.
- A le lo ifọsẹ kekere, ti kii ṣe abrasive lati yọ awọn abawọn alagidi diẹ sii.
- Ṣayẹwo awọn asopọ itanna ati ẹrọ lorekore ati rii daju pe wọn mọ, ailewu, pipe ati aabo.
- Ni iṣẹlẹ ti iṣoro kan, kan si alagbawo pẹlu eniyan ti o ni iwe-aṣẹ / oṣiṣẹ.
AWỌN NIPA
| Paramita \ Awoṣe | BLACKSTAR B.96 | SOLID Black (Semi-Clear) B.96 35(40) mm | BLACKSTAR Satin B.96 | MAGNUS B.108 |
| Awọn ipo idanwo | STC | STC | STC | STC |
| Agbara ipin | 455 W | 455 W | 445 W | 510 W |
| Itanna Data @STC | ||||
| Agbara to pọju (Pmax), W | 455 | 455 | 445 | 510 |
| Voltage ni Agbara to pọju (Vmpp), V | 29,71 | 29,71 | 29,40 | 33,34 |
| Lọwọlọwọ ni Agbara to pọju (Impp), A | 15,31 | 15,31 | 15,14 | 15,30 |
| Ṣii Circuit Voltage (Voc), V | 34,82 | 34,82 | 34,40 | 39,06 |
| Yika kukuru Lọwọlọwọ (Isc), A | 15,97 | 15,97 | 15,79 | 15,95 |
| Gbona Data | ||||
| Awọn iwọn otutu ti nṣiṣẹ | -40oC ÷ 85oC (-40°F ÷ 185°F) | -40oC ÷ 85oC (-40°F ÷ 185°F) | -40oC ÷ 85oC (-40°F ÷ 185°F) | -40oC ÷ 85oC (-40°F ÷ 185°F) |
| Olusodipupo iwọn otutu ti Pmax | -0,362%/°C (°F) | -0,362%/°C (°F) | -0,362%/°C (°F) | -0,362%/°C (°F) |
| Iwọn otutu olùsọdipúpọ ti Voc | -0,265%/°C (°F) | -0,265%/°C (°F) | -0,265%/°C (°F) | -0,265%/°C (°F) |
| Iṣatunṣe iwọn otutu ti Isc | +0,036% /° C (°F) | +0,036% /° C (°F) | +0,036% /° C (°F) | +0,036% /° C (°F) |
| Iwọn & data iwuwo | ||||
| Gigun | 1762 mm | 1762 mm | 1762 mm | 1961 mm |
| Ìbú | 1134 mm | 1134 mm | 1134 mm | 1134 mm |
| Sisanra | 30 mm | 35(40) mm | 30mm | 30 mm |
| Iwọn | 25,5 kg | 35 (36) kg | 25,5 kg | 28,5 kg |
| Iṣagbesori ọna | ||||
| Reference to the chapter | 3.3 | 3.3 | 3.3 | 3.3 |
| Omiiran | ||||
| Opo lọwọlọwọ yiyipada, A | 30 | |||
| Fire class, IEC 61730/UL 61730 | A/Iru II | |||
| O pọju eto voltage, V | 1500 | |||
Table 9. Electrical and mechanical parameters table.
| Paramita \ Awoṣe | OLODODO Semi- clear B.96 | SOLID Black B.96 | OLODODO Satin B.96 | OLODODO Agro B.64 |
| Awọn ipo idanwo | STC | STC | STC | STC |
| Agbara ipin | 455 W | 455 W | 445 W | 300 W |
| Itanna Data @STC | ||||
| Agbara to pọju (Pmax), W | 455 | 455 | 445 | 300 |
| Voltage ni Agbara to pọju (Vmpp), V | 29,71 | 29,71 | 29,40 | 19,60 |
| Lọwọlọwọ ni Agbara to pọju (Impp), A | 15,31 | 15,31 | 15,14 | 15,31 |
| Ṣii Circuit Voltage (Voc), V | 34,82 | 34,82 | 34,40 | 22,76 |
| Yika kukuru Lọwọlọwọ (Isc), A | 15,97 | 15,97 | 15,79 | 15,97 |
| Gbona Data | ||||
| Awọn iwọn otutu ti nṣiṣẹ | -40oC ÷ 85oC (-40°F ÷ 185°F) | -40oC ÷ 85oC (-40°F ÷ 185°F) | -40oC ÷ 85oC (-40°F ÷ 185°F) | -40oC ÷ 85oC (-40°F ÷ 185°F) |
| Olusodipupo iwọn otutu ti Pmax | -0,30%/°C (°F) | -0,30%/°C (°F) | -0,30%/°C (°F) | -0,30%/°C (°F) |
| Iwọn otutu olùsọdipúpọ ti Voc | -0,25%/°C (°F) | -0,25%/°C (°F) | -0,25%/°C (°F) | -0,25%/°C (°F) |
| Iṣatunṣe iwọn otutu ti Isc | +0,045% /° C (°F) | +0,045% /° C (°F) | +0,045% /° C (°F) | +0,045% /° C (°F) |
| Iwọn & data iwuwo | ||||
| Gigun | 1772 ± 2 mm | 1772 ± 2 mm | 1772 ± 2 mm | 1772 ± 2 mm |
| Ìbú | 1144 ± 2 | 1144 ± 2 | 1144 ± 2 mm | 1144 ± 2 mm |
| Sisanra | 7,2 mm | 7,2 mm | 7,2 mm | 7,2 mm |
| Iwọn | 33kg | 33 kg | 33 kg | 33 kg |
| Iṣagbesori ọna | ||||
| Reference to the chapter | 3.2 | 3.2 | 3.2 | 3.2 |
| Omiiran | ||||
| Opo lọwọlọwọ yiyipada, A | 30 | |||
| Fire class, IEC 61730/UL 61730 | A/Iru II | |||
| O pọju eto voltage, V | 1500 | |||
Table 10. Electrical and mechanical parameters table.
| Paramita \ Awoṣe | SOLID Satin B.96 35 mm | SOLID Satin B. 96 40 mm | SOLID AgroB.64 35 mm | SOLID AgroB.64 40 mm |
| Awọn ipo idanwo | STC | STC | STC | STC |
| Agbara ipin | 445 W | 445 W | 300 W | 300 W |
| Itanna Data @STC | ||||
| Agbara to pọju (Pmax), W | 445 | 445 | 300 | 300 |
| Voltage ni Agbara to pọju (Vmpp), V | 29,40 | 29,40 | 19,60 | 19,60 |
| Lọwọlọwọ ni Agbara to pọju (Impp), A | 15,14 | 15,14 | 15,31 | 15,31 |
| Ṣii Circuit Voltage (Voc), V | 34,40 | 34,40 | 22,78 | 22,78 |
| Yika kukuru Lọwọlọwọ (Isc), A | 15,79 | 15,79 | 15,97 | 15,97 |
| Gbona Data | ||||
| Awọn iwọn otutu ti nṣiṣẹ | -40oC ÷ 85oC (-40°F ÷ 185°F) | -40oC ÷ 85oC (-40°F ÷ 185°F) | -40oC ÷ 85oC (-40°F ÷ 185°F) | -40oC ÷ 85oC (-40°F ÷ 185°F) |
| Olusodipupo iwọn otutu ti Pmax | -0,362%/°C (°F) | -0,362%/°C (°F) | -0,30%/°C (°F) | -0,30%/°C (°F) |
| Iwọn otutu olùsọdipúpọ ti Voc | -0,265%/°C (°F) | -0,265%/°C (°F) | -0,25%/°C (°F) | -0,25%/°C (°F) |
| Iṣatunṣe iwọn otutu ti Isc | +0,036% /° C (°F) | +0,036% /° C (°F) | +0,045% /° C (°F) | +0,045% /° C (°F) |
| Iwọn & data iwuwo | ||||
| Gigun | 1762mm | 1762mm | 1762 mm | 1762 mm |
| Ìbú | 1134 mm | 1134 mm | 1134 mm | 1134 mm |
| Sisanra | 35 mm | 40 mm | 35 mm | 40 mm |
| Iwọn | 35 kg | 36kg | 35 kg | 36 kg |
| Iṣagbesori ọna | ||||
| Reference to the chapter | 3.3 | |||
| Omiiran | ||||
| Opo lọwọlọwọ yiyipada, A | 30 | |||
| Fire class, IEC 61730/UL 61730 | A/Iru II | |||
| O pọju eto voltage, V | 1500 | |||
Table 11.Electrical and mechanical parameters table.
- The electrical characteristics are within of the indicated values of ISC (φISC) ±3%, VOC (ϕVOC) ±3,5% and PMPP (ϕPmax) ±5%, under Standard Test Conditions (STC) (irradiance of 1000 W/m²,AM 1.5 spectrum, and a cell temperature of 25°C / 77°F)
- Gbogbo awọn panẹli SoliTek SOLID PV ni ibamu si kilasi aabo itanna II.
AlAIgBA ti layabiliti
- Niwọn igba ti ko ṣee ṣe fun SoliTek lati ṣakoso fifi sori ẹrọ, iṣiṣẹ, ohun elo ati itọju eto fọtovoltaic ni ibamu si itọnisọna yii. SoliTek ko ni gba ojuse ati ni gbangba layabiliti fun eyikeyi pipadanu, bibajẹ tabi inawo ti o dide lati tabi ni eyikeyi ọna ti a ti sopọ pẹlu iru fifi sori, isẹ, lilo tabi itọju.
- SoliTek will not take any responsibility for any possible violation of patent rights and third-party rights that are related to the application of the solar energy system. No permission of patents is given through implication.
- The information of this instruction is from the knowledge and experiences of SoliTek. However, the instructions and suggestions of this instruction do not make an external or internal of guarantee. SoliTek reserves the right to revise this instruction, products and all the information about products without prior notification to customers.
FAQ
- Q: What should I do before installing the PV modules?
- A: Read this entire guide, understand all instructions, and ensure compliance with all local, state, and federal regulations. Consult a certified building specialist for the structural integrity of the dwelling.
- Q: Can I install the PV modules myself without professional training?
- A: This documentation is not a complete installation manual for personnel not specifically trained in PV-modules. It serves as a general but strictly mandatory reference for the installer. Professional installation is highly recommended.
- Q: What happens if I don’t follow the instructions in this guide?
- A: Failure to follow instructions may damage system components, endanger personnel, damage property, or invalidate the panel warranty.
- Q: Is it safe to work on a rooftop during installation?
- A: Do not attempt to work on a rooftop until safety precautions have been identified and taken, including fall protection measures, ladders or stairways, and personal protective equipment (PPE). Avoid adverse conditions like strong winds or wet/frosted roofs.
- Q: How should I store the PV modules before installation?
- A: Store pallets in a cool and dry location until the PV modules are ready to be unpackaged. Do not exceed the maximum stacking height indicated on the packaging.