1. Ifihan
The SINOTIMER STVP series automatic over-voltage ati labẹ-voltage protector is designed for three-phase 3*127V/220VAC power systems with a rated working current of 80A. This device provides essential protection for electrical equipment by instantaneously cutting off the power supply when over-voltage, labẹ-voltage, or over-current conditions are detected. Once the circuit voltage returns to normal, the protector automatically restores power, ensuring continuous operation and safeguarding your appliances from damage.
This protector integrates multiple protection functions including over-voltage, labẹ-voltage, over-current, three-phase current (voltage) imbalance, phase sequence (reverse phase), zero-break, and phase-break protection. It also features voltmeter and ammeter functions, and the ability to restore factory settings. The device offers comprehensive features, stable performance, and ease of operation.
Iwe itọnisọna alaye olumulo ni ọna kika PDF wa fun igbasilẹ: Ilana olumulo (PDF)
2. Key Awọn ẹya ara ẹrọ
- Lori-voltage aabo
- Labẹ-voltage aabo
- Lori-lọwọlọwọ Idaabobo
- Imularada aifọwọyi
- Voltage display (separate ABC phase voltage wiwọn)
- Ampere display (separate ABC phase ampere measurement)
- Mẹta-alakoso ampere unbalance protection
- Ààbò ìtẹ̀lé ìpele (ààbò ìpele ìyípadà)
- Idaabobo fifọ ila odo
- Idaabobo ikuna alakoso
- Fault inquiry function
- Rotation display of voltage and current for each phase
- Adjustable over-voltage protection value and recovery value
- Adjustable under-voltage protection value and recovery value
- Adjustable over-current protection value and action time
- Adjustable 3-phase ampere unbalance protection value and action time
- Adjustable delay time after power-on
- Adjustable fault recovery delay time
- Factory data reset function
3. Awọn alaye ọja
| Iwa | Iye |
|---|---|
| Nọmba awoṣe | STVP936-1-80A |
| Ibi ti ina elekitiriki ti nwa | 3*127V/220VAC 60Hz |
| Oṣuwọn Voltage | 220V |
| Ipele | Ipele mẹta |
| O pọju. Fifuye Lọwọlọwọ | 1~80A Adjustable (default: 80A) |
| Lori-voltage Idaabobo Ibiti | 121V-150V-OFF Adjustable (default: 140V) |
| Lori-voltagIbiti Ìgbàpadà e | 120V-149V (default: 135V) |
| Lori-voltagÀkókò Ìṣe e | 0.1~10 seconds (default: 0.2s) |
| Labẹ-voltage Idaabobo Ibiti | 118V-80V-OFF Adjustable (default: 90V) |
| Labẹ-voltagIbiti Ìgbàpadà e | 118V-91V (default: 95V) |
| Labẹ-voltagÀkókò Ìṣe e | 0.1~10 seconds (default: 0.2s) |
| 3-Phase Volt Unbalance Protection | 10%~50%~OFF (default: 20%) |
| 3-Phase Volt Unbalance Action Time | 0.1~10 seconds (default: 1s) |
| Delay Time After Power-on | 2~255 seconds (default: 2s) |
| Fault Recovery Delay Time | 2~600 seconds (default: 60s) |
| Awoṣe Ifihan | LCD |
| Awọn iwọn | 71.5mm (W) * 95.2mm (H) * 65.7mm (D) |
| Fifi sori ẹrọ | 35mm DIN Rail |
| Ijẹrisi | CE, RoHS |
4. Alaye Aabo
- Fifi sori ẹrọ ati itọju yẹ ki o ṣe nipasẹ awọn oṣiṣẹ ina mọnamọna ti o peye nikan.
- Ensure the power supply is disconnected before any installation or wiring work.
- The device does not provide overload or short-circuit protection. It must be used in conjunction with appropriate external circuit breakers (e.g., C45, C65 mini circuit breakers) for comprehensive protection.
- Daju pe gbogbo awọn asopọ onirin wa ni aabo ati pe o tọ ṣaaju lilo agbara.
- Do not operate the device in wet or hazardous environments.
5. fifi sori
5.1 Ti ara Mefa

5.2 Iṣagbesori
The protector is designed for 35mm DIN rail installation. Snap the device onto the DIN rail securely.

5.3 Wiring aworan atọka
Connect the input and output terminals as shown in the diagram below. Ensure correct phase (L1, L2, L3) and neutral (N) connections. The input terminals are located at the top, and output terminals at the bottom.


6. Eto ati iṣeto ni
Lati tẹ ipo eto sii, tẹ mọlẹ SET button for 3 seconds. Then, continuously press SET to cycle through the parameters. Use the ▲ ati ▼ buttons to adjust the values. When "ENd" appears, press SET again to save the data and exit the setting mode.
If no operation is performed within 10 seconds after pressing SET, the device will automatically exit the setting mode, and any unsaved changes will be lost.
6.1 Parameter Settings Table
| Igbesẹ | Akoonu | Ifihan LCD | Description / Range (Default) |
|---|---|---|---|
| 1 | Lori-voltage Idaabobo iye | Uvo 280V | 221V-300V-OFF (280V) |
| 2 | Lori-voltage imularada iye | Uvor 250V | 220V-299V (250V) |
| 3 | Lori-voltage Idaabobo igbese akoko | 0.2S | 0.1-10s (0.2s) |
| 4 | Labẹ-voltage Idaabobo iye | Uve 160V | 219V-150V-OFF (160V) |
| 5 | Labẹ-voltage imularada iye | Uver 180V | 151V-220V (180V) |
| 6 | Labẹ-voltage Idaabobo igbese akoko | 0.2S | 0.1-10s (0.2s) |
| 7 | Lori-lọwọlọwọ Idaabobo iye | >In 80A | 1-80A (80A) |
| 8 | Over-current protection action time | 5S | 1-512s (5s) |
| 9 | 3 awọn ipele amp unbalance protection value | >In % | 5%-90%-OFF (25%). Not active if current < 2A. |
| 10 | 3 awọn ipele amp unbalance protection action time | Ọdun 1.0 S | 0.1-10s (1s) |
| 11 | Idaabobo ọkọọkan alakoso | ON ABC | ON or OFF (ON) |
| 12 | Agbara lori akoko idaduro | Ọdun 2 S | 2-255s (2s) |
| 13 | Fault recovery delay time | Ọdun 60 S | 2-512s (60s) |
| 14 | Fault inquiry code | E0 | Press ▲ to view last 5 fault records (E1-E5). >U for overvoltage, <U for undervoltage. |
| 15 | Ipari | Opin | Press SET to save and exit. |
6.2 Atunto ile-iṣẹ
To reset the device to factory settings, press and hold the ▲ ati ▼ awọn bọtini ni nigbakannaa fun 3 aaya.
7. Isẹ
Once installed and configured, the device will continuously monitor the three-phase power supply. The LCD screen will automatically rotate to display the real-time voltage and current for each phase (L1, L2, L3).
Ni irú ti ẹya lori-voltage, labẹ-voltage, or over-current event, the protector will automatically trip and cut off the power supply to protect connected equipment. After the fault condition clears and the recovery delay time has passed, the device will automatically restore power.
8. Laasigbotitusita
8.1 Fault Inquiry
If a fault occurs, the device will display an error code (E0). You can press the ▲ button to query the last 5 fault records (E1-E5). The display will indicate:
- ">U" for overvoltage awọn iṣẹlẹ.
- "<U" for undervoltage awọn iṣẹlẹ.
8.2 Phase Sequence Error
If the LCD displays "ABC" character, it indicates a phase sequence error. To correct this, arbitrarily reverse any two of the three phase lines (L1, L2, L3) at the input.
9. Itọju
- Jeki ẹrọ naa di mimọ ati ofe kuro ninu eruku ati ọrinrin.
- Máa ṣàyẹ̀wò àwọn ìsopọ̀ wáyà déédéé fún bí ó ṣe le tó àti àmì ìbàjẹ́ tàbí ìbàjẹ́.
- Do not attempt to repair the device yourself. Refer to qualified personnel for service.
10. Atilẹyin ọja ati Support
For technical support, inquiries, or warranty claims, please contact the distributor:
Pin kakiri: XNY INTERNATIONAL LIMITED
Adirẹsi: Room 20A, Kiu Fu Commercial Building, 300 Lockhart Road, Wanchai, Hong Kong.
Tẹli: 0086 57761733853
Faksi: 0086 577 89736991
WhatsApp: 0086 1565857 3377
Wechat: sinotimer
Skype: sinotimer
Web: www.sinotimer.com
Imeeli: info@sinotimer.com