Ọdun 0063010

Ìwé Ìtọ́ni Ìtọ́ni Ìdábòbò Ìparẹ́ Ìparẹ́ Watts 009M2 (Àwòṣe 0063010)

For Models: 009M2, 009M2-QT

1. Ifihan

This manual provides detailed instructions for the installation, operation, and maintenance of the Watts 009M2 Reduced Pressure Zone (RPZ) Backflow Preventer. This device is designed to protect potable water supplies from contamination due to backpressure or backsiphonage from non-potable sources. It is crucial to read and understand all instructions before installation and use to ensure proper function and safety.

The Watts 009M2 RPZ assembly features a compact, modular design for easy maintenance, with a single access cover for in-line repairs. It is suitable for continuous pressure piping applications and cross-connections identified as health hazards.

2. Alaye Aabo pataki

3. Ọja Ipariview ati irinše

The Watts 009M2 Reduced Pressure Zone Backflow Preventer is constructed with a durable bronze body and features NPT end connections. Key components include:

Watts 009M2 Reduced Pressure Zone Backflow Preventer
Figure 1: Watts 009M2 Reduced Pressure Zone Backflow Preventer. This image shows the bronze body, quarter-turn shutoff valves with green handles, and multiple test cocks on top.

4. Eto ati fifi sori

  1. Ṣayẹwo fifi sori ẹrọ tẹlẹ:
    • Verify that the product model (009M2) and size (2 inch) match your requirements.
    • Ṣe àyẹ̀wò ẹ̀rọ náà fún ìbàjẹ́ èyíkéyìí tí ó bá ṣẹlẹ̀ sí ọkọ̀ ojú omi.
    • Ensure all necessary tools and materials for installation are available.
  2. Igbaradi Aaye:
    • Choose an installation location that allows for easy access for testing and maintenance.
    • Ensure adequate drainage for the relief valve discharge.
    • The device should be installed horizontally, with the relief valve pointing downwards.
  3. Asopọ Pipa:
    • Flush the upstream piping thoroughly to remove any debris before connecting the backflow preventer.
    • Connect the inlet and outlet piping to the NPT connections on the device. Use appropriate thread sealant.
    • Avoid overtightening connections to prevent damage to the bronze body.
    • Ensure the flow arrow on the device body matches the direction of water flow.
  4. Relief Valve Drain:
    • Connect a drain line to the relief valve outlet. The drain line must be adequately sized and sloped to allow for free discharge and prevent backpressure on the relief valve.
    • Ensure the drain line terminates in an air gap, preventing any possibility of cross-connection.
  5. Ṣayẹwo fifi sori lẹhin:
    • Slowly open the upstream shutoff valve, then the downstream shutoff valve, to gradually fill the system and prevent water hammer.
    • Ṣayẹwo gbogbo awọn asopọ fun awọn n jo.
    • Perform initial testing by a certified backflow prevention tester to ensure proper operation and compliance with local codes.

5. Awọn ilana Iṣiṣẹ

The Watts 009M2 is designed for continuous pressure operation. Normal operation involves the device being fully open, allowing water to flow through the system while providing backflow protection.

6. Itọju

Regular maintenance is critical for the reliable performance of your backflow preventer. The modular design and single access cover simplify servicing.

7. Laasigbotitusita

IsoroOwun to le FaOjutu
Water discharge from relief valve (continuous)
  • Fouled first check valve
  • Damaged relief valve seat or disc
  • Excessive backpressure
  • Clean or repair first check valve.
  • Inspect and replace relief valve components.
  • Identify and correct source of backpressure.
Ko si ṣiṣan omi tabi sisan ti o dinku
  • Shutoff valves closed
  • Debris obstructing flow
  • Fouled check valves
  • Ensure shutoff valves are fully open.
  • Isolate and inspect for debris.
  • Clean or repair check valves.
N jo lati awọn asopọ
  • Improperly sealed threads
  • Damaged gaskets
  • Re-apply thread sealant and tighten connections.
  • Inspect and replace gaskets.

For issues not listed or if troubleshooting steps do not resolve the problem, contact a certified plumbing professional or Watts technical support.

8. Awọn pato

Nọmba awoṣe0063010 (009M2)
Backflow Preventer TypeApejọ Agbegbe Ipa ti o dinku
Ohun elo araIdẹ
Inlet/Outlet Connection Size2 Inches (50 MM)
Inlet/Outlet Connection TypeFemale Threaded NPT
O pọju Ṣiṣẹ Ipa175 PSI (Pẹpẹ 12.10)
Iwọn otutu ti o pọju180°F (82°C)
Iwon otutu33°F (0.5°C)
Iru IdaaboboBackpressure and Backsiphonage
Awọn iwọn Ọja (L x W x H)22 x 10 x 8 inches
Iwọn Nkan27 iwon
Lead Free StatusNO (For non-potable use only)

9. Atilẹyin ọja ati Support

Specific warranty information for Watts products is typically provided with the product packaging or available on the official Watts website. Please refer to these resources for the most current warranty terms and conditions.

For technical support, replacement parts, or further assistance, please contact Watts customer service or visit their official website. Ensure you have your product model number (0063010) and serial number (if applicable) ready when contacting support.

Watts Official Webojula: www.watts.com

Awọn iwe aṣẹ ti o jọmọ - 0063010

Ṣaajuview Ìlànà Ìṣètò Ìgbìmọ̀ Ẹ̀rọ Ìpàdé Ìpínlẹ̀ Ìfúnpá Watts LF909 Series
Ìlànà ìmọ̀ ẹ̀rọ tó péye fún Ìpàdé Watts LF909 Series Reduced Pressure Zone (21⁄2" - 10"). Àwọn ẹ̀ya ara ẹ̀rọ, iṣẹ́, àwọn ohun èlò, ìwọ̀n, àti agbára fún ẹ̀rọ ìdènà Lead Free backflow yìí pẹ̀lú sensọ ìkún omi tó ṣọ̀kan.
Ṣaajuview Watts Series 009, LF009, LFU009, SS009, U009: Ìwé Ìtọ́sọ́nà fún Fífi sori ẹrọ, Ìtọ́jú, àti Àtúnṣe
This comprehensive manual from Watts provides essential guidance for the installation, maintenance, and repair of the Series 009, LF009, LFU009, SS009, and U009 Reduced Pressure Zone Assemblies. It details safety warnings, installation procedures, inspection, servicing, troubleshooting, and warranty information for these critical backflow prevention devices.
Ṣaajuview Ìwé Ìtọ́sọ́nà fún Àwọn Àkójọpọ̀ Watts Series 909, LF909, 909RPDA.
Ìtọ́sọ́nà pípé fún fífi sori ẹrọ, ìtọ́jú, àti àtúnṣe Watts Series 909, LF909, àti 909RPDA Reduced Pressure Zone Assemblies, pẹ̀lú àwọn ìkìlọ̀ ààbò, àwọn ìlànà ìfisílé, àwọn ìlànà ìdánwò, àwọn ìtọ́ni ìtọ́jú, ìṣòro, àti ìwífún nípa àtìlẹ́yìn.
Ṣaajuview Awọn apejọ Agbegbe Ipa Ti o dinku Watts Series LF909 - Awọn alaye imọ-ẹrọ
Àwọn àlàyé ìmọ̀-ẹ̀rọ tó ṣe kedere fún àwọn àkójọpọ̀ Watts Series LF909 Reduced Pressure Zone Assemblies, pẹ̀lú àwọn ẹ̀yà ara rẹ̀, iṣẹ́ rẹ̀, ìwọ̀n rẹ̀, ìwọ̀n rẹ̀, àti agbára rẹ̀. A ṣe é fún ìṣàkóso ìsopọ̀pọ̀ omi tó ṣeé mu.
Ṣaajuview Ìwé Ìtọ́sọ́nà fún Àkójọpọ̀ Watts Series 009, LF009, LFU009, SS009, U009.
Comprehensive guide for the installation, maintenance, and repair of Watts Series 009, LF009, LFU009, SS009, and U009 Reduced Pressure Zone Assemblies, covering safety, installation procedures, annual inspection, troubleshooting, and service. Includes details on flood sensor activation and connection kits.
Ṣaajuview Watts Series LF919 Reduced Pressure Zone Assembly: Installation, Maintenance, and Repair Manual
Comprehensive guide for installing, maintaining, and repairing the Watts Series LF919 Reduced Pressure Zone Assembly (1/2" - 2"). Includes safety warnings, installation procedures, servicing instructions, and troubleshooting.