STI STI-1100

Ìwé Ìtọ́sọ́nà Olùlò STI-1100 STI-1100 II pẹ̀lú Ìbòrí Ìbòrí Horn Flush Mount

Model: STI-1100

Brand: Safety Technology International, Inc. (STI)

1. Ọja Ipariview

The STI-1100 Stopper II is a protective polycarbonate cover designed to deter false fire alarms while allowing legitimate access. This flush-mount device features an integrated horn that sounds when the cover is lifted, alerting personnel to potential misuse. Its robust construction provides protection against physical damage and tampsisun.

STI-1100 Stopper II front view

Nọmba 1: Iwaju view of the STI-1100 Stopper II protective cover. This image displays the clear polycarbonate cover with the red alarm housing visible at the top, featuring the text 'IN CASE OF FIRE - LIFT ACTIVATE FIRE ALARM' and 'LIFT HERE' at the bottom.

2. Eto ati fifi sori

The STI-1100 Stopper II is designed for flush mounting over existing fire alarm pull stations. Proper installation ensures optimal protection and functionality.

2.1 irinše

  • Polycarbonate Ideri
  • Fireemu Fifi
  • Integrated Horn (95 dB or 105 dB)
  • Cable connecting cover to frame
  • Batiri (pẹlu)
  • Ohun elo iṣagbesori (skru)

2.2 fifi sori Igbesẹ

  1. Mura Ilẹ Iṣagbesori: Ensure the surface around the fire alarm pull station is clean and flat for proper flush mounting.
  2. Fi fireemu naa si: Place the mounting frame over the fire alarm pull station. Ensure it aligns correctly and does not obstruct the pull station's operation.
  3. Ṣe aabo fireemu naa: Use the provided mounting hardware to securely attach the frame to the wall. Do not overtighten.
  4. Fi Batiri sii: Open the alarm housing (typically located within the red section) and insert the included battery, observing correct polarity.
  5. So Ideri: Connect the polycarbonate cover to the frame via the integrated cable. Snap the cover onto the frame, ensuring it closes securely.
  6. Iṣe idanwo: Briefly lift the cover to ensure the horn sounds. Close the cover to verify the horn stops.
STI-1100 Stopper II side view showing flush mount

Nọmba 2: Apa view of the STI-1100 Stopper II, illustrating its flush-mount design. This image shows the depth and how the unit sits against a wall.

3. Awọn ilana Iṣiṣẹ

The STI-1100 Stopper II operates as a deterrent and protective cover for fire alarm pull stations.

  • Ise deede: The clear polycarbonate cover remains closed, protecting the fire alarm pull station from accidental activation or tampsisun.
  • Gbigbe itaniji: When the cover is lifted to gain access to the fire alarm pull station, the integrated horn will sound. This alerts nearby personnel to the potential activation of the fire alarm.
  • Horn Deactivation: The horn will stop sounding once the cover is snapped back onto the frame.
  • Legitimate Alarm Activation: In a genuine emergency, lift the cover, activate the fire alarm pull station, and then close the cover.

4. Itọju

Regular maintenance ensures the continued reliability and functionality of your STI-1100 Stopper II.

  • Battery Function Check: The end user must verify the alarm and battery function every six months. Briefly lift the cover to ensure the horn sounds clearly.
  • Rirọpo Batiri: Replace the battery annually or as required if the horn sounds weak during the function check. Use a 9V battery (included with the unit).
  • Ninu: Clean the polycarbonate cover with a soft, damp cloth. Avoid abrasive cleaners that could scratch the surface.
  • Ayewo ti ara: Periodically inspect the cover and frame for any signs of damage or wear. Ensure the cable connecting the cover to the frame is intact.

5. Laasigbotitusita

If you encounter issues with your STI-1100 Stopper II, refer to the following common troubleshooting steps:

  • Iwo Ko Ndún:
    • Check the battery. Ensure it is correctly installed and not depleted. Replace if necessary.
    • Verify that the cover is fully lifted to trigger the alarm mechanism.
  • Cover Not Securing Properly:
    • Inspect the mounting frame and cover for any obstructions or damage that might prevent proper closure.
    • Ensure the frame is securely mounted to the wall and not loose.
  • Weak Horn Sound:
    • This typically indicates a low battery. Replace the battery immediately.

For issues not resolved by these steps, please contact STI customer support.

6. Awọn pato

Ẹya ara ẹrọẸ̀kúnrẹ́rẹ́
Nọmba awoṣeSti-1100
BrandSTI (Safety Technology International, Inc.)
Iṣagbesori IruẸke Fula
Ohun eloPolycarbonate
Àwọ̀Red (Alarm Housing), Clear (Cover)
Ipele Ohun95 dB tàbí 105 dB
Orisun agbaraBattery (12 Volts DC)
Awọn iwọn otutu ti nṣiṣẹ-40°F si 120°F (-40°C si 49°C)
Iwọn (Ọja)5 x 3.19 x 6.5 inches
Iwọn Nkaniwon 1 (ounje 16)
Awọn iwe-ẹriUL Ti ṣe atokọ si AMẸRIKA ati awọn iṣedede aabo Ilu Kanada

7. atilẹyin ọja Information

Safety Technology International, Inc. provides the following warranty for the STI-1100 Stopper II:

  • Polycarbonate Housing: Lifetime guarantee against breakage in normal use.
  • Awọn paati Itanna: Atilẹyin ọdun kan.

This warranty covers defects in materials and workmanship under normal use. It does not cover damage resulting from misuse, abuse, unauthorized modification, or improper installation.

8. Atilẹyin ati Olubasọrọ

For technical assistance, warranty claims, or further information regarding your STI-1100 Stopper II, please contact Safety Technology International, Inc. directly.

Olupese: Safety Technology International, Inc.

Please refer to the official STI webAaye tabi apoti ọja fun awọn alaye olubasọrọ tuntun julọ.

Awọn iwe aṣẹ ti o jọmọ - Sti-1100

Ṣaajuview STI Stop II Series: Ideri Idaabobo fun Awọn Ibudo Itaniji Ina - Fifi sori ẹrọ ati Awọn alaye ni pato
Comprehensive guide to the STI Stopper II Series protective cover for manual fire alarm pull stations. Features include physical damage protection, optional audible alarm, weather resistance (NEMA 3R), and ADA compliance. Details installation steps, specifications, testing approvals, and maintenance.
Ṣaajuview Ìtọ́sọ́nà Fífi Sílẹ̀ Ohun Èlò Ìdènà Ẹ̀gbin STI-8100/STI-8130
Ìtọ́sọ́nà ìfisílé gbogbogbò àti ìwífún nípa ọjà fún àwọn STI-8100 àti STI-8130 STI Ibajẹ Detector láti ọ̀dọ̀ Safety Technology International. Kọ́ nípa àwọn ẹ̀yà ara rẹ̀, ìwọ̀n rẹ̀, àwọn ìgbésẹ̀ ìfisílé rẹ̀, àti àwọn ìkìlọ̀ pàtàkì.
Ṣaajuview STI Universal Stopper fifi sori Itọsọna: STI-13000 & STI-14000 Series
Itọsọna fifi sori okeerẹ fun awọn awoṣe STI Universal Stopper STI-13000 ati STI-14000, awọn pato ti o bo, awọn aṣayan iṣagbesori, awọn alaye iwo, ati alaye ailewu.
Ṣaajuview STI Universal Stopper STI-13000 & STI-14000 Series fifi sori Itọsọna
Itọsọna fifi sori ẹrọ ati awọn pato fun awọn awoṣe STI Universal Stopper STI-13000 ati jara STI-14000, ibora awọn akọsilẹ fifi sori ẹrọ, awọn alaye imọ-ẹrọ, awọn aṣayan iṣagbesori, wiwiri, ati atilẹyin ọja.
Ṣaajuview Iduro ijade STI: Aabo ati Ẹrọ Idena ole
Kọ ẹkọ nipa STI Exit Stopper (STI-6400 jara), ẹrọ aabo to wapọ ti a ṣe lati ṣe idiwọ ole ati gbigbọn si awọn ijade laigba aṣẹ tabi awọn titẹ sii nipasẹ awọn ilẹkun pajawiri. Awọn ẹya pẹlu awọn itaniji adijositabulu, ikole ti o tọ, ati fifi sori ẹrọ rọrun.
Ṣaajuview STI-6400WIR Series Exit Stopper fifi sori ẹrọ ati awọn ẹya ara ẹrọ
Itọsọna okeerẹ si STI-6400WIR Series Exit Stopper, ṣe alaye awọn ẹya ara ẹrọ rẹ, awọn pato, awọn ilana fifi sori ẹrọ, ati awọn eto yipada fun aabo ẹnu-ọna imudara ati iṣakoso itaniji.