Johnson Controls EP-8000-3

Ìwé Ìtọ́sọ́nà Olùlò Ẹ̀rọ Ìyípadà Pneumatic Electro Johnson Controls EP-8000-3

Awoṣe: EP-8000-3 | Brand: Awọn iṣakoso Johnson

1. Ọja Ipariview

The Johnson Controls EP-8000-3 is an electro-pneumatic transducer designed to convert a standard electrical input signal into a proportional pneumatic output signal. Specifically, it accepts a 4-20 mA DC electrical input and produces a 3-15 PSIG pneumatic output. This device is crucial in industrial control systems for interfacing electronic controllers with pneumatic actuators or other pneumatic equipment. It features a low volume output, ensuring precise and responsive control.

Image of Johnson Controls EP-8000 series electro-pneumatic transducer, showing model EP-8000-2, a gray cylindrical device with electrical and pneumatic connections.

This image displays a Johnson Controls electro-pneumatic transducer, specifically the EP-8000-2 model, which is representative of the EP-8000 series. It is a compact, gray cylindrical unit designed for converting electrical signals to pneumatic signals. Visible features include the brand name 'JOHNSON CONTROLS', model number 'EP-8000-2', input/output specifications, and connection points at the base.

2. Alaye Aabo

Read and understand all instructions before installing, operating, or maintaining this device. Failure to follow these instructions may result in property damage, personal injury, or death.

  • Fifi sori ẹrọ ati iṣẹ gbọdọ jẹ nipasẹ oṣiṣẹ ti o peye nikan.
  • Disconnect all power sources before wiring or servicing the transducer.
  • Ensure pneumatic supply lines are depressurized before making or breaking connections.
  • Verify that the operating environment is within the specified temperature and humidity ranges.
  • Do not exceed the maximum rated input current or output pressure.

3. Eto ati fifi sori

3.1 Iṣagbesori

Mount the EP-8000-3 transducer in a location free from excessive vibration, moisture, and extreme temperatures. Ensure adequate space for wiring and pneumatic connections, as well as for future maintenance. The device should be mounted securely to prevent movement during operation.

3.2 Electrical Awọn isopọ

Connect the 4-20 mA DC input signal to the designated electrical terminals. Observe proper polarity. Use appropriate gauge wiring for the application and ensure all connections are secure to prevent intermittent operation or signal loss. Refer to the device's labeling for specific terminal assignments.

3.3 Pneumatic Awọn isopọ

Connect the regulated pneumatic supply (typically 20 PSIG for a 3-15 PSIG output range) to the supply port. Connect the output pneumatic line to the designated output port. Ensure all pneumatic connections are leak-free using appropriate fittings and sealing methods. The pneumatic supply must be clean, dry, and oil-free instrument air.

4. Isẹ

Once properly installed and connected, the EP-8000-3 transducer will convert the incoming 4-20 mA DC electrical signal into a proportional 3-15 PSIG pneumatic output. A 4 mA input will correspond to a 3 PSIG output, and a 20 mA input will correspond to a 15 PSIG output. The transducer operates continuously as long as power and pneumatic supply are provided.

4.1 Calibration (if applicable)

While the EP-8000-3 is factory calibrated, periodic verification of its output against a known input signal is recommended. If field calibration is required, consult the specific calibration procedure outlined in the full technical data sheet or contact Johnson Controls technical support. Typically, calibration involves adjusting zero and span settings to ensure accurate conversion across the full range.

5. Itọju

The EP-8000-3 transducer is designed for reliable operation with minimal maintenance. However, regular inspection can help ensure optimal performance and longevity.

  • Ayewo Igbakọọkan: Visually inspect the transducer and its connections for any signs of damage, corrosion, or loose wiring/tubing.
  • Mimọ: Keep the exterior of the device clean and free from dust or debris. Do not use harsh chemicals or abrasive cleaners.
  • Pneumatic Supply Quality: Ensure the pneumatic supply remains clean, dry, and oil-free. Contaminants can affect the transducer's performance and lifespan.
  • Iduroṣinṣin asopọ: Periodically check electrical and pneumatic connections for tightness.

6. Laasigbotitusita

If the EP-8000-3 transducer is not functioning as expected, consider the following troubleshooting steps:

AisanOwun to le FaIṣe
No pneumatic outputNo electrical input signal; No pneumatic supply; Faulty wiring/tubing; Device failureVerify 4-20 mA input; Check pneumatic supply pressure; Inspect connections; Replace device if necessary
Incorrect pneumatic outputIncorrect input signal; Calibration drift; Incorrect pneumatic supply pressureVerify 4-20 mA input signal accuracy; Check pneumatic supply pressure; Perform calibration if required
Unstable pneumatic outputFluctuating input signal; Unstable pneumatic supply; Loose connections; VibrationCheck stability of input signal and pneumatic supply; Secure all connections; Reduce vibration if possible

If troubleshooting steps do not resolve the issue, contact Johnson Controls technical support for further assistance.

7. Awọn pato

  • Awoṣe: EP-8000-3
  • Olupese: Johnson idari
  • Ibuwọlu Input: 4-20 mA DC
  • Ifihan agbara Ijade: 3-15 PSIG
  • Orisi Ijade: Iwọn kekere
  • Iru ọja: Electro Pneumatic Transducer
  • ASIN: B005KWHVMS
  • Ọjọ Akọkọ Wa: Oṣu kọkanla ọjọ 8, ọdun 2019

8. Atilẹyin ọja ati Support

Specific warranty terms and conditions for the Johnson Controls EP-8000-3 transducer are not detailed within this manual. For information regarding product warranty, technical support, or service, please refer to the official Johnson Controls website or contact your authorized Johnson Controls distributor or sales representative. Ensure you have the product model number (EP-8000-3) and purchase details available when seeking support.

Awọn iwe aṣẹ ti o jọmọ - EP-8000-3

Ṣaajuview Johnson Ṣàkóso EP-8000 Series Electro-Pneumatic Transducers: Àwọn Ìlànà Ìmọ̀-ẹ̀rọ, Fífi sori ẹrọ, àti Iṣẹ́
Ìwé ìròyìn ìmọ̀-ẹ̀rọ tó kún rẹ́rẹ́ fún àwọn ẹ̀rọ amúṣẹ́dá EP-8000 Series ti Johnson Controls. Ó bo ọjà náà lórí rẹ̀.view, iṣiṣẹ́, ìwọ̀n, fifi sori ẹrọ, okun waya, iwọntunwọnsi, ati awọn alaye imọ-ẹrọ fun awọn ohun elo iṣakoso ile-iṣẹ.
Ṣaajuview Johnson dari AD-XXX Series PureFlow Duplex Air Compressors | Iwe itẹjade ọja
Comprehensive product bulletin detailing the Johnson Controls AD-XXX Series PureFlow Duplex Air Compressors, ranging from 1/2 to 20 hp. Includes features, technical specifications, performance data, ordering information, dimensions, wiring diagrams, and a complete list of repair parts.
Ṣaajuview Hx 3 Fọwọkan iboju Itanwo Alaye Alaye olumulo
Iwe afọwọkọ alaye olumulo yii n pese awọn itọnisọna alaye ati itọsọna fun Johnson Controls Hx 3 Touch Screen Thermostat (Awoṣe: S1-THXU430W), fifi sori fifi sori ẹrọ, awọn ẹya, iṣẹ ṣiṣe, Asopọmọra app, ati awọn eto.
Ṣaajuview Awọn ohun elo Smart n ṣakoso Itọsọna Ibẹrẹ kiakia fun Awọn ọna ṣiṣe HVAC UCB
Comprehensive quick start guide for Johnson Controls Smart Equipment Unit Control Board (UCB) HVAC systems. Learn setup, navigation, firmware updates, configuration backup, commissioning, and troubleshooting for Constant Volume, VAV, Economizer, and Heat Pump applications. Includes detailed menu structures and operational parameters.
Ṣaajuview Smart Equipment™ Awọn iṣakoso Itọsọna Ibẹrẹ kiakia - Firmware 3.4 ati Agbalagba
Itọsọna ibẹrẹ iyara fun Awọn iṣakoso Awọn ohun elo Smart (ẹya 3.4 ati famuwia agbalagba), iṣeto alaye, awọn imudojuiwọn famuwia, lilọ kiri, ati iṣeto ni fun awọn eto iṣakoso HVAC.
Ṣaajuview Ọpa MCL 5.3 fifi sori ẹrọ ati Itọsọna Ibẹrẹ - Awọn iṣakoso Johnson
Itọsọna okeerẹ fun fifi sori ẹrọ ati ṣeto sọfitiwia ati ohun elo ohun elo MCL Awọn iṣakoso Johnson 5.3, awọn atunto eto ibora, iṣeto nẹtiwọọki, ati awọn ilana ibẹrẹ ibẹrẹ.