The STI FS200 SpecSeal Ready Sleeve Kit is engineered to provide a UL Classified and code-compliant firestop penetration for cables through fire-rated walls or floors. This kit offers a complete solution, simplifying the installation process and ensuring fire safety compliance.

The FS200 sleeve is suitable for installation in barriers up to 10 inches (250 mm) thick. When properly installed, the sleeve maintains the fire resistance rating of the barrier, preventing the spread of fire and smoke.

2. Alaye Aabo

Adherence to safety guidelines is crucial during installation. Always observe the following precautions:

  • Nigbagbogbo wọ ohun elo aabo ti ara ẹni ti o yẹ (PPE), pẹlu awọn gilaasi aabo ati awọn ibọwọ.
  • Rii daju pe agbegbe iṣẹ jẹ afẹfẹ daradara.
  • Consult local building codes and fire safety regulations to ensure compliance.
  • Do not modify the product in any way not specified in these instructions.
  • This product is intended for new cable installations only and cannot be used to retrofit existing violations without proper assessment by a qualified professional.

3. Ọja Ipariview

3.1 irinše

The STI FS200 Ready Sleeve Kit includes the following components:

  • 2-inch (51 mm) Sleeve (galvanized steel)
  • Escutcheon Plates
  • Gasket
  • Firestop Putty

3.2 Awọn ẹya ara ẹrọ

Key features of the FS200 kit include:

  • Provides a comprehensive, UL Classified solution for cable penetrations.
  • Eliminates the need for cutting conduit and strut, saving installation time.
  • Designed for quick and efficient installation.
  • No external caulking is required for sealing.
STI FS200 2-inch firestop sleeve kit components

Nọmba 1: The STI FS200 2-inch firestop sleeve kit. This image displays the main components of the kit, including the galvanized steel sleeve, escutcheon plates, and securing hardware.

4. Eto ati fifi sori

Follow these steps for proper installation of the STI FS200 Firestop Sleeve Kit:

  1. Mura Ṣii silẹ: Create a circular opening in the fire-rated wall or floor. A 2.5-inch hole saw is recommended for optimal fit. For accurate alignment, predrill with a smaller bit before using the hole saw.
  2. Insert the Sleeve: Position the 2-inch sleeve within the prepared opening. The sleeve should be centered within the barrier, extending an equal distance from both sides of the wall or floor.
  3. Awọn eroja to ni aabo: Place the gaskets and escutcheon plates onto the sleeve on both sides of the barrier. Secure them firmly using the provided hardware. Ensure a snug fit against the barrier surface.
  4. Apply Firestop Putty: Use the provided firestop putty to seal any remaining annular space between the sleeve and the opening, and around any cables passing through the sleeve. Ensure a complete and tight seal to prevent the passage of smoke and fire.
  5. Fifi sori ẹrọ USB: Route cables through the installed sleeve. Ensure that the cables do not exceed the fill capacity of the sleeve and that the firestop putty maintains its seal around all cables.

Akiyesi pataki: This system is designed for new cable installations. Retrofitting existing penetrations may require different methods or additional firestop materials. Consult relevant firestop listings and local codes.

5. Awọn ilana Iṣiṣẹ

The STI FS200 Firestop Sleeve Kit functions as a passive fire protection system. Once correctly installed, it operates continuously to maintain the fire resistance rating of the penetrated barrier. There are no active operational steps required for the sleeve itself.

Its primary function is to prevent the passage of flame, smoke, and hot gases through openings created for cables in fire-rated constructions.

6. Itọju

To ensure the continued effectiveness of the firestop system, periodic inspection and maintenance are recommended:

  • Ayẹwo igbagbogbo: Visually inspect the firestop sleeve and the surrounding firestop material at regular intervals, or as required by local codes. Check for any signs of damage, degradation, or dislodgement.
  • Iduroṣinṣin Di: Verify that the firestop putty around the cables and between the sleeve and the barrier remains intact and provides a complete seal.
  • Cable Modifications: If cables are added, removed, or modified, ensure that the firestop system is re-sealed according to the manufacturer's instructions and relevant firestop listings to maintain its fire rating.
  • Atunṣe ibajẹ: Any damage to the sleeve or firestop material should be repaired immediately using approved STI firestop products and methods.

7. Laasigbotitusita

This section addresses common issues that may arise during or after installation:

  • Issue: Sleeve not fitting correctly in the opening.
    Ojutu: Verify that the hole size in the barrier is approximately 2.5 inches. Ensure the barrier thickness does not exceed the maximum 10-inch limit for the FS200 sleeve.
  • Issue: Visible gaps or openings around the sleeve or cables after installation.
    Ojutu: Reapply or add additional firestop putty to completely fill all annular spaces and ensure a tight, continuous seal around the sleeve and all cables.
  • Issue: Concerns about fire code compliance.
    Ojutu: Review the installation against the specific UL Classified listings for the STI FS200. Consult local fire safety authorities or a qualified firestop contractor for verification and guidance.

8. Awọn pato

SipesifikesonuẸ̀kúnrẹ́rẹ́
Nọmba awoṣeFS200
OlupeseSTI (Specified Technologies Inc.)
Sleeve Size2 inches (51 mm) Trade Size
Maximum Barrier Thickness10 inches (250 mm)
ASINB079DWV4TC
Akọkọ Wa ỌjọOṣu Kẹta Ọjọ 6, Ọdun 2012

9. Atilẹyin ọja ati Support

For detailed warranty information regarding the STI FS200 Firestop Sleeve Kit, please refer to the official documentation provided by Specified Technologies Inc. (STI) or visit their official webojula.

For technical support, product inquiries, or assistance with specific application requirements, please contact STI customer service directly through their official channels.

Awọn iwe aṣẹ ti o jọmọ - FS200

Ṣaajuview STI Universal Stopper STI-13000 & STI-14000 Series fifi sori Itọsọna
Itọsọna fifi sori ẹrọ ati awọn pato fun awọn awoṣe STI Universal Stopper STI-13000 ati jara STI-14000, ibora awọn akọsilẹ fifi sori ẹrọ, awọn alaye imọ-ẹrọ, awọn aṣayan iṣagbesori, wiwiri, ati atilẹyin ọja.
Ṣaajuview STI Aago / Belii bibajẹ Stopper ati Waya Guard Catalog
Aabo Imọ-ẹrọ International (STI) n pese awọn ilana fifi sori ẹrọ fun STI-9635, STI-9636, ati STI-9637 Aago/Bell bibajẹ Duro. Iwe naa tun ṣe ẹya atokọ okeerẹ ti awọn oluso okun waya STI fun ọpọlọpọ awọn ohun elo pẹlu awọn aṣawari ẹfin, awọn sensọ PIR, awọn ami ijade, awọn ina pajawiri, awọn beakoni, awọn olugbohunsafẹfẹ, ati awọn lilo oriṣiriṣi, apejuwe awọn nọmba awoṣe ati awọn iwọn.
Ṣaajuview STI Smoke Detector Wire Guards: Installation Guide and Product Catalog
Comprehensive guide to STI Smoke Detector Wire Guards, including installation instructions, certifications, service information, and a catalog of available models with dimensions. These guards protect smoke detectors from damage, vandalism, and environmental factors while ensuring proper functionality.
Ṣaajuview STI Universal Stopper fifi sori Itọsọna: STI-13000 & STI-14000 Series
Itọsọna fifi sori okeerẹ fun awọn awoṣe STI Universal Stopper STI-13000 ati STI-14000, awọn pato ti o bo, awọn aṣayan iṣagbesori, awọn alaye iwo, ati alaye ailewu.
Ṣaajuview STI Stop II Series: Ideri Idaabobo fun Awọn Ibudo Itaniji Ina - Fifi sori ẹrọ ati Awọn alaye ni pato
Comprehensive guide to the STI Stopper II Series protective cover for manual fire alarm pull stations. Features include physical damage protection, optional audible alarm, weather resistance (NEMA 3R), and ADA compliance. Details installation steps, specifications, testing approvals, and maintenance.
Ṣaajuview STI Irin Web Stoppers® - Protective Cages for Smoke Detectors
Durable STI Steel Web Stoppers® from Safety Technology International provide robust protection for smoke detectors against vandalism and accidental damage. Featuring patented octagonal web design, corrosion-resistant materials, and UL, CSFM, and MEA approvals, these guards ensure reliable performance in controlled environments.