1. Ifihan
This manual provides essential instructions for the safe and efficient installation, operation, and maintenance of your RANCO Electronic Temperature Control unit. This device is designed to provide precise temperature regulation for heating, cooling, and refrigeration applications, featuring a liquid crystal display (LCD) for constant temperature readout and diagnostic error codes.
2. Alaye Aabo
ÌKÌLỌ̀: Ewu Ìjayà Iná mànàmáná. Yọ agbára kúrò kí o tó fi sori ẹrọ tàbí kí o ṣe iṣẹ́.
- Fifi sori ẹrọ ati iṣẹ gbọdọ jẹ nipasẹ oṣiṣẹ ti o peye nikan.
- Rii daju pe gbogbo onirin ni ibamu pẹlu awọn koodu itanna agbegbe ati ti orilẹ-ede.
- Daju awọn ipese agbara voltage matches the unit's specifications (120/208/240VAC).
- Do not operate the unit if it appears damaged.
- The enclosure type is NEMA 1, suitable for indoor use, providing protection against falling dirt.
3. Ọja Ipariview
The RANCO Electronic Temperature Control is a versatile line voltage thermostat equipped with an LCD for clear temperature display and operational feedback. It includes features such as keypad lockout, memory for settings, and a time delay on power-up to protect connected equipment.

Nọmba 1: RANCO Electronic Temperature Control unit. This image displays the gray rectangular control unit featuring an LCD screen and three control buttons (SET, Up, Down) on its front panel. A gray cable exits from the top, and another gray cable with a black cylindrical temperature sensor extends from the bottom. The unit's casing is secured by screws at its corners.
4. Eto ati fifi sori
4.1 Iṣagbesori
Mount the control unit in a location that is easily accessible for viewing and operation, and where it is protected from moisture and excessive vibration. Ensure the NEMA 1 enclosure rating is appropriate for the environment.
4.2 Onirin
Connect the control unit to the appropriate power supply (120/208/240VAC) and to the controlled equipment (heating, cooling, or refrigeration system) according to the wiring diagram provided with the unit. The unit features one SPDT (Single Pole Double Throw) relay for output control. Ensure all connections are secure and insulated.
4.3 Sensọ Placement
The thermistor sensor (1/4" diameter, 2" length) should be placed in the area where temperature is to be monitored. Ensure the sensor is not exposed to direct drafts or heat sources that could provide inaccurate readings. The sensor cable should be routed to avoid damage or interference.
5. Awọn ilana Iṣiṣẹ
5.1 Agbara soke
Upon initial power-up, the unit will undergo a time delay before operation begins. The LCD will display the sensed temperature.
5.2 Eto otutu
- Tẹ awọn SET button to enter the setpoint adjustment mode.
- Lo awọn Up ati Isalẹ arrow buttons to adjust the desired temperature setpoint.
- Tẹ SET again to confirm and save the new setpoint, or wait a few seconds for the unit to automatically save and exit.
5.3 Adjusting Differential
The differential (hysteresis) can be set between 1 and 30 degrees Fahrenheit. Refer to the full product manual for specific steps to access and adjust this parameter, as it typically involves a combination of button presses.
5.4 Titiipa oriṣi bọtini
The unit features a keypad lockout function to prevent unauthorized changes to settings. Consult the detailed product manual for instructions on how to activate and deactivate this feature.
5.5 Awọn koodu aṣiṣe
The LCD display will show specific error codes if a problem is detected, particularly related to refrigeration. Refer to the comprehensive product manual for a list of error codes and their corresponding troubleshooting steps.
6. Itọju
- Jeki ẹyọ naa di mimọ ati ofe kuro ninu eruku ati idoti. Lo asọ asọ ti o gbẹ fun mimọ.
- Periodically inspect wiring connections for tightness and signs of wear.
- Ensure the temperature sensor is clean and properly positioned.
- No user-serviceable parts are inside the unit. Refer all repairs to qualified service personnel.
7. Laasigbotitusita
- Ko si Ifihan: Check power supply connections. Ensure the unit is receiving the correct voltage.
- Kika iwọn otutu ti ko tọ: Verify sensor placement and ensure it is not damaged. Check for proper sensor connection.
- Unit Not Controlling: Check setpoint and differential settings. Verify wiring to the controlled equipment. Look for any error codes on the display.
- Awọn koodu aṣiṣe Ti han: Consult the full product manual for specific error code definitions and recommended actions.
If problems persist after performing these checks, contact qualified service personnel.
8. Awọn pato
| Ẹya ara ẹrọ | Sipesifikesonu |
|---|---|
| Nkan | Itanna otutu Iṣakoso |
| Yipada Iru | SPDT |
| Yipada Iṣe | Open/Close on Rise |
| Voltage Ibiti | 120/208 / 240VAC |
| Ibiti Iṣakoso | -30°F si 220°F |
| Iyatọ | 1°F de 30°F |
| Number of Relay Inputs | 1 |
| Number of Relay Outputs | 1 |
| Ni kikun fifuye Amps @ 120VAC | 16A (NO), 5.8A (NC) |
| Ni kikun fifuye Amps @ 240VAC | 8A (NO), 2.9A (NC) |
| Sensọ Iru | Themmistor |
| Sensing Bulb Diameter | 1/4" |
| Sensing Bulb Length | 2" |
| Apade Iru | AKESE 1 |
| Giga | 6-1/2" |
| Ìbú | 2-3/4" |
| Ijinle | 2-1/2" |
| Àwọ̀ | Grẹy |
| Ifihan Iru | LCD |
| Awọn iwe-ẹri | Àkójọpọ̀ UL, CSA fọwọ́ sí |
| Awọn ohun elo | Heating, Cooling, Refrigeration |
9. Atilẹyin ọja ati Support
For warranty information and technical support, please refer to the documentation provided with your purchase or contact Ranco customer service directly. Keep your purchase receipt as proof of purchase.





