1. Ifihan
The SINOTIMER MC101-611 is a universal intelligent temperature control meter designed for precise temperature and humidity management. It features a clear LCD display for process value (PV) and set value (SV), along with various output and alarm functions. This manual provides essential information for the safe and effective operation of your device.

olusin 1.1: Iwaju view of the MC101-611 Temperature Control Meter, showing the dual digital display and control buttons.
2. Alaye Aabo
- Ka gbogbo awọn ilana ni pẹkipẹki ṣaaju fifi sori ẹrọ ati ṣiṣẹ.
- Rii daju pe ipese agbara voltage bá àwọn ohun tí ẹ̀rọ náà béèrè mu (85-265V AC, 50/60Hz).
- All wiring should be performed by a qualified electrician to prevent electric shock or damage to the device.
- Má ṣe lo ẹ̀rọ náà ní àyíká tí ọrinrin, eruku tàbí àwọn afẹ́fẹ́ tó ń ba nǹkan jẹ́ pọ̀ jù.
- Disconnect power before performing any maintenance or wiring changes.
- Pa ẹrọ naa mọ kuro ninu idamu itanna ti o lagbara.
3. Awọn ẹya Ọja
- Universal input for various temperature sensors (K, J, E, T, R, S, B, Pt100, Cu50).
- Dual digital display for Process Value (PV) and Set Value (SV).
- Multiple control outputs: Relay and SSR (Solid State Relay).
- Alarm functions (AL1, AL2) for high/low limits.
- PID auto-tuning function for precise control.
- Ibiti iwọn otutu iṣiṣẹ jakejado.
- Compact and easy-to-install design.
4. Package Awọn akoonu
- 1 x SINOTIMER MC101-611 Temperature Control Meter
- 1 x Mounting Bracket (as shown in Figure 4.1)
- 1 x Itọsọna olumulo (iwe yii)

Figure 4.1: The MC101-611 unit alongside its included mounting bracket, essential for panel installation.
5. Eto
5.1 Iṣagbesori
The MC101-611 is designed for panel mounting. Cut an appropriate opening in your control panel and insert the meter. Secure it from the rear using the provided mounting bracket. Ensure a snug fit to prevent vibration.
5.2 Onirin
Refer to the wiring diagram on the side of the unit and Figure 5.1 for correct connections. Ensure all connections are secure and insulated. Incorrect wiring can damage the device or pose a safety hazard.
- Àwọn ibùdó 1 àti 2: AC Power Supply (85-265V AC, 50/60Hz)
- Àwọn ibùdó 3 àti 4: Main Output (OUT) - Normally Open (NO) and Normally Closed (NC) contacts for Relay output.
- Àwọn ibùdó 6 àti 7: Alarm Output (ALM) - Relay contacts for alarm.
- Àwọn ibùdó 8, 9, àti 10: Sensor Input (RTD/TC) - Connect your temperature sensor here. Refer to the sensor's manual for correct polarity/connection type.
- Àwọn ibùdó 11 àti 12: SSR Output - For connecting to a Solid State Relay.

Figure 5.1: Detailed wiring diagram on the side of the MC101-611, indicating connections for power, output, alarm, and sensor input.
6. Awọn ilana Iṣiṣẹ
6.1 Ifihan Loriview
The meter features a dual display:
- PV (Iye ilana): The upper red display shows the current measured temperature/humidity.
- SV (Iye Ṣètò): The lower green display shows the desired set point.
- Atọka OUT: Illuminates when the main output is active.
- AT Atọka: Illuminates when the auto-tuning function is active.
- Àwọn Àmì AL1/AL2: Illuminate when Alarm 1 or Alarm 2 conditions are met.
6.2 bọtini Awọn iṣẹ
- Ṣeto Bọtini: A lo lati tẹ ipo eto paramita sii ati jẹrisi awọn yiyan.
- < / R/S Button: Used to shift digits during setting or to reset alarms.
- ▼ (Isalẹ) Bọtini: Decreases the value of a parameter or set point.
- ▲ (Soke) Bọtini: Increases the value of a parameter or set point.
6.3 Setting the Temperature/Humidity Set Point (SV)
- Ni ipo iṣẹ deede, tẹ bọtini naa SET button once. The SV display will begin to flash.
- Lo awọn ▲ (Soke) ati ▼ (Down) buttons to adjust the SV to your desired value. Use the < / R/S button to shift the cursor for faster adjustment.
- Tẹ awọn SET button again to confirm the new SV and exit the setting mode.
6.4 To ti ni ilọsiwaju paramita Eto
To access advanced parameters (e.g., input type, control mode, alarm settings, PID parameters), press and hold the SET button for approximately 3-5 seconds until the first parameter code appears on the PV display. Use the ▲ (Soke) ati ▼ (Down) buttons to navigate through parameters and the SET button to enter and confirm values. Refer to the detailed parameter list in the full technical manual for specific codes and their functions.
7. Itọju
- Ninu: Nu iboju naa ki o si casinpẹ̀lú aṣọ rírọ̀ tí ó gbẹ. Má ṣe lo àwọn ohun ìfọṣọ tàbí àwọn ohun èlò ìfọṣọ.
- Ayewo: Lokọọkan ṣayẹwo awọn asopọ onirin fun alaimuṣinṣin tabi ipata.
- Ibi ipamọ: If storing the device for an extended period, ensure it is kept in a dry, dust-free environment within its specified storage temperature range.
8. Laasigbotitusita
| Isoro | Owun to le Fa | Ojutu |
|---|---|---|
| Ifihan jẹ òfo | No power supply; Incorrect wiring; Device fault. | Ṣayẹwo awọn asopọ agbara ati voltage; Verify wiring according to diagram; Contact support if problem persists. |
| Ìfihàn PV fi 'HHHH' tàbí 'LLLL' hàn | Sensor open circuit (HHHH) or short circuit (LLLL); Sensor not connected; Incorrect sensor type setting. | Check sensor wiring; Ensure sensor is connected; Verify sensor type setting in parameters matches connected sensor. |
| Ijade ko ṣiṣẹ | SV not reached; Control mode incorrect; Output wiring issue. | Adjust SV; Check control mode (e.g., heating/cooling); Verify output wiring. |
| Kika iwọn otutu ko pe | Sensor calibration needed; Sensor damaged; External interference. | Perform sensor calibration (if supported); Replace sensor; Relocate device away from interference sources. |
9. Awọn pato

Figure 9.1: Product label on the side of the MC101-611, detailing model, range, output, and power supply specifications.
| Paramita | Iye |
|---|---|
| Awoṣe | MC101-611 |
| Ibiti o | 0-1300°C K (Configurable for various sensor types) |
| Iwọn otutu | Celsius/Fahrenheit (Selectable) |
| Abajade | Relay/SSR |
| Itaniji | ALM1 |
| Ipese Voltage | 85-265V AC, 50/60Hz |
| Ifihan Iru | LCD |
| Iwọn Nkan | 5.1 iwon |
| Package Mefa | 3.9 x 2.8 x 2.4 inches |
10. Atilẹyin ọja ati Support
This product comes with a standard manufacturer's warranty. Please refer to your purchase documentation for specific warranty terms and conditions. For technical support, troubleshooting assistance, or warranty claims, please contact the SINOTIMER customer service through the retailer where the product was purchased or visit the official SINOTIMER webojula fun alaye olubasọrọ.