Olutọju iwọn otutu ti ọpọlọ E62 PID

Brainchild-E62-PID-Temperature-Controller- product

Pariview & Irisi

Brainchild-E62-PID-Temperature-Controller- (2)

Awọn bọtini ati awọn ifihan

IṢẸ KEYPAD

KỌKỌRIN YI: Brainchild-E62-PID-Temperature-Controller- (3)
Bọtini yii ni a lo lati yan paramita lati jẹ viewed tabi ṣatunṣe.

KỌKỌRỌ SOKE/Ilọsi:Brainchild-E62-PID-Temperature-Controller- (4)
Yi bọtini ti wa ni lo lati mu awọn iye ti awọn ti o yan paramita.

KỌKỌRỌ IWAJU/Dinku:  Brainchild-E62-PID-Temperature-Controller- (5)
Bọtini yii ni a lo lati dinku iye paramita ti o yan.

KOKO SHIFT:Brainchild-E62-PID-Temperature-Controller- (6)
A lo bọtini yii lati:

  • Move to the digit of the selected parameter and change the value by using up or down key to increase or decrease the value.

Yi lọ Soke: Brainchild-E62-PID-Temperature-Controller- (7)
Awọn bọtini meji ti a tẹ ni iṣọkan ni a lo lati:

  • Go to the previous parameter

Tun: + Brainchild-E62-PID-Temperature-Controller- (8)
Awọn bọtini meji ti a tẹ ni iṣọkan ni a lo lati:

  • Yi ifihan pada si iboju ile.
  • Tun itaniji dimu to ni kete ti o ti yọ ipo itaniji kuro.
  • Duro ipo iṣakoso afọwọṣe, Iyipada-iyipada aifọwọyi tabi ipo isọdiwọn.
  • Ko ohun-Tuning laifọwọyi tabi ifiranṣẹ aṣiṣe ibaraẹnisọrọ kuro.
  • Enter the manual control menu if a failure mode occurs.

Yi lọ si isalẹ: Brainchild-E62-PID-Temperature-Controller- (9)
Two keys pressed synchronously directly go to the Manual control mode

Tẹ bọtini: Brainchild-E62-PID-Temperature-Controller- (3)
Tẹ Brainchild-E62-PID-Temperature-Controller- (3) ki o si mu fun iṣẹju-aaya 5 tabi ju bẹẹ lọ si:

  • Enter the Auto-Tuning mode. Brainchild-E62-PID-Temperature-Controller- (10) Ifihan yoo han.
  • Enter the manual control mode. Brainchild-E62-PID-Temperature-Controller- (11) Ifihan yoo han.
    Enter the setup menu mode. Brainchild-E62-PID-Temperature-Controller- (12)Ifihan yoo han.
  • Brainchild-E62-PID-Temperature-Controller- (13) Perform calibration of a selected parameter during the calibration procedure. The display will show

Akojọ Flowchart

Akojọ aṣayan ti pin si awọn ẹgbẹ marun. Wọn jẹ bi wọnyi:

  1. Olumulo Akojọ
  2. Auto-Tuning Mode Menu
  3. Afowoyi Ipo Akojọ aṣyn
  4. Akojọ Akojọ aṣyn
  5. Calibration Mode Menu

Brainchild-E62-PID-Temperature-Controller- (14)

  • Tẹ Brainchild-E62-PID-Temperature-Controller- (3) for the next parameter ; Press Brainchild-E62-PID-Temperature-Controller- (3) ati Brainchild-E62-PID-Temperature-Controller- (4) bọtini lati pada si paramita ti tẹlẹ.
  • Tẹ mọlẹBrainchild-E62-PID-Temperature-Controller- (3) for 3.1 seconds, then let go to select auto tuning mode.
  • Tẹ mọlẹ Brainchild-E62-PID-Temperature-Controller- (3)for 4.2 seconds, then let go, to select manual control mode.
  • Tẹ mọlẹ Brainchild-E62-PID-Temperature-Controller- (3)for 5.3 seconds, then let go to select setup mode.
  • Tẹ mọlẹ Brainchild-E62-PID-Temperature-Controller- (3) fun awọn aaya 6.4, lẹhinna jẹ ki lọ lati yan ipo isọdiwọn.

Olumulo Akojọ
Lo Brainchild-E62-PID-Temperature-Controller- (3) key to enter basic menu parameters, and press  Brainchild-E62-PID-Temperature-Controller- (3) again to select SP1, SEL1~SEL8.
Tẹ  Brainchild-E62-PID-Temperature-Controller- (3)Brainchild-E62-PID-Temperature-Controller- (4) lati pada si išaaju.

Brainchild-E62-PID-Temperature-Controller- (15)

Auto-Tuning Mode
Tẹ Brainchild-E62-PID-Temperature-Controller- (3) key 5 seconds to activate Auto-Tuning Mode

Brainchild-E62-PID-Temperature-Controller- (16)

Afowoyi Ipo Akojọ aṣyn
Tẹ Brainchild-E62-PID-Temperature-Controller- (3) key 3 seconds to execute the selected default program

Brainchild-E62-PID-Temperature-Controller- (17)

Enter Manual Control Mode; refer to Manual 6.1 & 6.8.2~6.8.4

Brainchild-E62-PID-Temperature-Controller- (18)

Akojọ Akojọ aṣyn
The setup menu has been categorized into eight categories.
They are listed as below.

  1. Akojọ aṣayan ipilẹ (bASE)
  2. Akojọ aṣyn jade (oUT)
  3. Communication Menu (CoMM)
  4. User Select Menu (SEL)

Akojọ aṣayan ipilẹ (bASE)
Lo Brainchild-E62-PID-Temperature-Controller- (4)orBrainchild-E62-PID-Temperature-Controller- (5) key to get bASE in the lower display then use Brainchild-E62-PID-Temperature-Controller- (3) key to enter to basic menu parameters.

Brainchild-E62-PID-Temperature-Controller- (19)

Akojọ aṣyn jade (oUT)
Lo Brainchild-E62-PID-Temperature-Controller- (4)orBrainchild-E62-PID-Temperature-Controller- (5) key to get oUT in the lower display then use Brainchild-E62-PID-Temperature-Controller- (3) key to enter to output menu parameters.

Brainchild-E62-PID-Temperature-Controller- (20)

Communication Menu (CoMM)
Lo Brainchild-E62-PID-Temperature-Controller- (4)orBrainchild-E62-PID-Temperature-Controller- (5) key to get CoMM in the lower display then use Brainchild-E62-PID-Temperature-Controller- (3) key to enter to communication menu parameters.
Please note that confirm A2FN set to CoMM when using communication.

Brainchild-E62-PID-Temperature-Controller- (21)

User Select Menu (SEL)
Lo Brainchild-E62-PID-Temperature-Controller- (4)orBrainchild-E62-PID-Temperature-Controller- (5) key get SEL in the lower display then use Brainchild-E62-PID-Temperature-Controller- (3) key to enter to select the user menu parameters.

Brainchild-E62-PID-Temperature-Controller- (22)

Ipo odiwọn

Brainchild-E62-PID-Temperature-Controller- (24)

Tẹ Brainchild-E62-PID-Temperature-Controller- (3) key for 2 seconds or longer (not more than 3 seconds) ; then release it to enter calibration Mode.
Tẹ Brainchild-E62-PID-Temperature-Controller- (3) key for 5 seconds to perform calibration

  • Please note that it is required to use specialized equipment to apply calibration, attempting to change will affect device accuracy

Akiyesi:

  • Using Manual, Auto-Tuning, Calibration modes will break the control loop and change some of the previous setting data. Make sure that the system is allowable to apply these modes.
  • The flow chart shows a complete list of all parameters. For actual application, the number of available parameters will vary depending on the setup and model of the controller and will be less than that shown in the flow chart.
  • The user can select up to 8 parameters to put in the user select menu by using the SEL1~SEL8 parameters in the setup menu

Ṣaaju ki o to Bẹrẹ, Ṣeto Input/Ojade
Lẹhin ti agbara soke, tẹ mọlẹ Brainchild-E62-PID-Temperature-Controller- (3) for 5.3 seconds, then let go to enter Setup Menu. Complete Parameter setting, INPT, UNIT, DP, O1TY, O1L and O1H.

  • Enter the Setup Menu. Press Brainchild-E62-PID-Temperature-Controller- (3) for 5 seconds to enter Basic Menu (bASE). Finish setting for INPT, UNIT and DP. Exit the level.
  •  Return to the Setup Menu. Press Brainchild-E62-PID-Temperature-Controller- (3) for 5 seconds to enter Output Menu (oUT). Finish setting for O1TY, O1L and O1H. Press and hold Brainchild-E62-PID-Temperature-Controller- (4) Brainchild-E62-PID-Temperature-Controller- (5)  ati pada si oju-ile.

Brainchild-E62-PID-Temperature-Controller- (25)

OP1L / OP1H Table

Ibiti o OP1L OP1H
OM9A-3 4-20 20.0 100.0
OM9A-3 0-20 0.0 100.0
OM9A-5 0-5V 0.0 50.0
OM9A-5 1-5V 10.0 50.0
OM9A-5 0-10 0.0 100.0

* When O1TY as DC.MA or  DC. Vo, set the value based on usage requirement

Asopọ ebute

Brainchild-E62-PID-Temperature-Controller- (1)

Parimeter akiyesi

User Menu Parameter

Modbus Paramita Apejuwe Ibiti o Aiyipada Wiwọle
0 SP1 Ṣeto Ojuami 1 Kekere: SP1L

Iwọn giga: SP1H

25.0 °C R/W
64 PV Iye ilana Kekere: -19999

ti o ga: 45536

(77.0°F) R
65 SV Lọwọlọwọ ṣeto ojuami iye Kekere: SP1L

Iwọn giga: SP1H

—— R
44  

SEL1

Yan paramita 1st fun akojọ aṣayan olumulo 0 KOSI

1 A1SP

2 A2SP

3 TItiipa

4 INPT

5 PB

6 TI

7 TD

8 SHIF

9 OFST

10 O1HY

11 A1HY

12 A2HY

13 ADDR

—— R/W
45 SEL2 Select 2nd parameter Select 2nd parameter for user manual. Same as the SEL1 0 R/W
46 SEL3 Select 3rd parameter Select 3rd parameter for user manual. Same as the SEL1 0 R/W
47 SEL4 Select 4th parameter Select 4th parameter for user manual. Same as the SEL1 0 R/W
48 SEL5 Select 5th parameter Select 5th parameter for user manual. Same as the SEL1 0 R/W
49 SEL6 Select 6th parameter Select 6th parameter for user manual. Same as the SEL1 0 R/W
50 SEL7 Select 7th parameter Select 7th parameter for user manual. Same as the SEL1 0 R/W
51 SEL8 Select 8th parameter Select 8th parameter for user manual. Same as the SEL1 0 R/W

Manual Mode Parameter

Modbus Paramita Apejuwe Ibiti o Aiyipada Wiwọle
66 MV1 Ijade 1% Iye Kekere: 0.00

ga: 100.00%

—– R (R/W,

Afọwọṣe)

Basic (bASE) Parameter

Modbus Paramita Apejuwe Ibiti o Aiyipada Wiwọle
3 Titiipa Yan paramita lati wa ni titiipa 0 Kò: Ko si paramita ti wa ni titiipa

1  SEt: Setup data are locked

2 uSEr: Setup data and user data are locked. SetPoint are unlocked.

3  ALL: All data are locked

0 R/W
4 INPT Input sensor selec- tion 0 J_tC: J iru Thermocouple

1 K_tC: K iru Thermocouple

2 t_tC: T type Thermocouple

3 R_tC: R iru Thermocouple

4 S_tC: S type Thermocouple

5 Pt. dN: PT 100 DIN

6 Pt.JS: PT 100 JIS

1 R/W
5 UNIT Aṣayan titẹ sii 0 oC: °C unit

1 oF: °F unit

0 R/W
6 DP Decimal point selec- tion 0 No.dP: no decimal point

1 1-dP: 1 aaye eleemewa

 

1

 

R/W

 

9

 

SP1L

Low iye to ṣeto ojuami iye Kekere:

J_TC: -120.0°C (-184.0°F)

K_TC: -200.0°C (-328.0°F)

T_TC: -250.0°C (-418.0°F) R_TC: 0.0°C ( 32.0°F) S_TC: 0.0°C ( 32.0°F) PTDN: -200.0°C (-328.0°F)

PTJS: -200.0°C (-328.0°F)

Iwọn giga: SP1H

-17.8 °C

(0.0°F)

 

R/W

10  

SP1H

Ga iye to ti ṣeto ojuami iye Kekere: SP1L

Ga:

J_TC: 1000.0°C (1828.0°F) K_TC: 1370.0°C (2498.0°F) T_TC: 400.0°C ( 752.0°F) R_TC: 1767.7°C (3214.0°F) S_TC: 1767.7°C (3214.0°F) PTDN: 850.0°C (1562.0°F) PTJS: 600.0°C (1112.0°F)

537.8 °C

(1000.0°F)

 

R/W

12 FILT  

Àlẹmọ damping time constant of PV

0 0: 0 iṣẹju-aaya akoko igbagbogbo

1 0.2: 0.2 iṣẹju-aaya akoko igbagbogbo

2 0.5: 0.5 iṣẹju-aaya akoko igbagbogbo

3 1: 1 iṣẹju-aaya akoko igbagbogbo

4 2: 2 iṣẹju-aaya akoko igbagbogbo

5 15: 5 iṣẹju-aaya akoko igbagbogbo

6 10: 10 iṣẹju-aaya akoko igbagbogbo

7 20: 20 iṣẹju-aaya akoko igbagbogbo

8 30: 30 iṣẹju-aaya akoko igbagbogbo

9 60: 60 iṣẹju-aaya akoko igbagbogbo

2 R/W
14 PB Iwọn iye

iye

Kekere: 0.0

Giga: 500.0°C (900.0°F)

10.0 °C

(18.0°F)

R/W
15 TI Integral akoko iye Low: 0, High: 3600 sec 60 R/W
16 TD Iye akoko itọsẹ Low: 0, High: 360.0 sec 30.0 R/W
11 SHIF PV shift (offset)

iye

Low: -200.0°C (-360.0°F) High: 200.0°C (360.0°F) 0.0 °C

(0.0°F)

R/W
68 CICF CIC àlẹmọ yipada 0 PAA

1 LORI

0 R

Output (oUT) Parameter

Modbus Paramita Apejuwe Ibiti o Aiyipada Wiwọle
17 JADE1 Iṣẹjade 1 0 REVR: Reverse (heating) control action

1 dIRt: Direct (cooling) control action

0 R/W
21 CYC1 Jade 1 ọmọ akoko Low: 0.1;

Giga: 90.0 iṣẹju-aaya.

18.0 R/W
18 O1TY O wu 1 ifihan agbara iru 0 RELY: Ijadejade yii

1SSrd: Ri to ipinle yiyi wakọ wakọ

2 DC.MA: DC current

3 DC.Vo: DC voltage

0 R/W
7 OP1L OP1 laini o wu kekere iye iye 0.0 ~ OP1H 0.0 R/W
8 OP1H OP1 linear output

high limit value

OP1L ~ 110.0% 100.0 R/W
19 O1FT Ipo gbigbe ikuna 1 jade 0~1000: 0.0 ~ 100.0 % to continue output 1

control function if the sensor fails, or select OFF (0) or ON (1) for ON-OFF control

0.0 R/W
22 OFST Offset value for P

iṣakoso

Kekere: 0

ga: 100.0%

25.0 R/W
20 O1HY Output 1 ON-OFF

control hysteresis

Kekere: 0.1

Giga: 50.0°C (90.0°F)

0.5 °C

(0.9°F)

R/W
23 PL1L MV1 power value

iwọn kekere

Kekere: 0

Iwọn giga: 50% tabi PL1H

0 R/W
24 PL1H MV2 power value limit high Kekere: PL1L

ga: 100%

 

100

 

R/W

25 A1FN Itaniji 1 iṣẹ fun itaniji 1 o wu 0 Bẹẹkọ: Ko si iṣẹ itaniji

1 dE.HI: Itaniji giga iyapa

2 dE.Lo: Itaniji kekere iyapa

3 db.HI: Deviation band out of band alarm

4 db.Lo: Ẹgbẹ iyapa ni itaniji band

5 PV.HI: Ilana iye ga itaniji

6 PV.Lo: Ilana iye kekere itaniji

 

1

 

R/W

Modbus Paramita Apejuwe Ibiti o Aiyipada Wiwọle
 

26

 

A1MD

 

Alarm 1 operation mode

0 NoRM: Iṣe itaniji deede

1 LtCH: Latching alarm action

2 HoLd: Mu iṣẹ itaniji duro

3 Lt.Ho: Latching & Mu igbese

0 R/W
29 A1HY Alarm 1 Hysteresis control Kekere: 0.1

Giga: 50.0°C (90.0°F)

0.1 °C

(0.2°F)

R/W
34 A1DL Itaniji 1 idaduro Kekere: 0; ga: 5999 iṣẹju-aaya 0 R/W
28 A1FT Alarm 1 failure trans- fer mode 0 oFF: OFF if sensor fails

1 lori: ON ti sensọ ba kuna

1 R/W
1 A1SP Itaniji 1 ṣeto ojuami A1FN=PVHI/PVLO

Kekere: SP1L Giga: SP1H

100.0 °C

(212.0°F)

R/W
13 A1DV Alarm 1 deviation value A1FN=DEHI/DELO/DBHI/DBLO

Kekere: 0.0 Giga: 500.0°C (900.0°F)

10.0 °C

(18.0°F)

R/W
33  

A2FN

 

Itaniji 2 iṣẹ fun itaniji 2 o wu

0 Bẹẹkọ: Ko si iṣẹ itaniji

1 dE.HI: Itaniji giga iyapa

2 dE.Lo: Itaniji kekere iyapa

3 db.HI: Deviation band out of band alarm

4 db.Lo: Ẹgbẹ iyapa ni itaniji band

5 PV.HI: Ilana iye ga itaniji

6 PV.Lo: Ilana iye kekere itaniji

7 COMM: RS485

 

2

R/W
 

35

 

A2MD

 

Alarm 2 operation mode

0 NoRM: Iṣe itaniji deede

1 LtCH: Latching alarm action

2 HoLd: Mu iṣẹ itaniji duro

3 Lt.Ho: Latching & Mu igbese

 

0

 

R/W

36 A2HY Hysteresis control of alarm 2 Kekere: 0.1°C

Giga: 50.0°C (90.0°F)

0.1 °C

(0.2°F)

R/W
38 A2DL Itaniji 2 idaduro Kekere: 0; ga: 5999 iṣẹju-aaya 0 R/W
37 A2FT Alarm 2 failure forced transfer mode 0 oFF: Alarm output OFF if sensor fails

1 oN: Alarm output ON if sensor fails

1 R/W
2 A2SP Itaniji 2 ṣeto ojuami A2FN=PVHI/PVLO

Kekere: SP1L Giga: SP1H

100.0 °C

(212.0°F)

R/W
43 A2DV Alarm 2 deviation value A2FN=DEHI/DELO/DBHI/DBLO

Kekere: 0.0 Giga: 500.0°C (900.0°F)

10.0 °C

(18.0°F)

R/W

Communication (CoMM) Parameter

Modbus Paramita Apejuwe Ibiti o Aiyipada Wiwọle
39 ADDR Address assignment of digital
ibaraẹnisọrọ
Kekere: 1

ti o ga: 255

1 R/W
40 BAUD Baud oṣuwọn ti oni ibaraẹnisọrọ 0   2.4: 2.4 Kbits/s baud rate

1   4.8: 4.8 Kbits/s baud rate

2   9.6: 9.6 Kbits/s baud rate

3  14.4: 14.4 Kbits/s baud rate

4  19.2: 19.2 Kbits/s baud rate

5  28.8: 28.8 Kbits/s baud rate

6  38.4: 38.4 Kbits/s baud rate

7  57.6: 57.6 Kbits/s baud rate

8  115.2: 115.2 Kbits/s baud rate

2 R/W
41 DATA Data bit count of dig- ital communication 0bIt: 7 die-die

1bIt: 8 die-die

1 R/W
42 PARI The parity bit of digi- tal communication 0 EVEN: Even parity

1  odd: Odd parity

2 NoNE: No parity bit

 

0

 

R/W

Calibration Mode Parameter

Modbus Paramita Apejuwe Ibiti o Aiyipada Wiwọle
52 ADLO mV calibration low

olùsọdipúpọ

Kekere: -1999

ti o ga: 1999

 

—–

 

R/W

53 ADHI mV calibration high

olùsọdipúpọ

Kekere: -1999

ti o ga: 1999

 

—–

 

R/W

54 RTDL RTD calibration low

olùsọdipúpọ

Kekere: -1999

ti o ga: 1999

 

—–

 

R/W

55 RTDH RTD calibration high coefficient Kekere: -1999

ti o ga: 1999

 

—–

 

R/W

56 CJLO Cold junction calibra-

tion low coefficient

Kekere: -5.00

ti o ga: 40.00

 

—–

 

R/W

Miiran Paramita

Modbus Paramita Apejuwe Ibiti o Aiyipada Wiwọle
57 CJCT Tutu Junction otutu Kekere: -4000

ti o ga: 9000

—– R
58 DATE Ọjọ Low: 0;

ti o ga: 65535

—– R
59 SRNO Nomba siriali Low: 0;

ti o ga: 65535

—– R
63 CJCL Cold junction low calibration

voltage

Kekere: 0

ti o ga: 7552

—– R
69 EROR Koodu aṣiṣe Kekere: 0; ti o ga: 65535 —– R
70 MODE Ipo isẹ & ipo itaniji Kekere: 0

ti o ga: 65535

—– R
71 PROG Device version, firmware version 67.XX —– R
72 Kaadi afinihan Koodu aṣẹ Kekere: 0; ti o ga: 65535 —– R/W
73 JOB1 Koodu iṣẹ Kekere: 0; ti o ga: 65535 —– R/W

Koodu aṣiṣe

Asise Koodu Ifihan

Aami

 

Apejuwe & Idi

 

Atunse Iṣe

10 ER10 Aṣiṣe ibaraẹnisọrọ: koodu iṣẹ buburu Correct the communication software to meet the protocol

awọn ibeere

11 ER11 Aṣiṣe ibaraẹnisọrọ: forukọsilẹ adirẹsi ni ibiti o ti le Ma ṣe fun ọmọ-ọdọ naa ni adiresi ti o tobi ju ti iforukọsilẹ silẹ
14 ER14 Communication error: attempt to write a

read-only data

Maṣe kọ data kika-nikan tabi data to ni aabo si ẹrú naa
15 ER15 Aṣiṣe ibaraẹnisọrọ: kọ iye ti ko ni ibiti o wa si iforukọsilẹ Maṣe kọ data ti o ju iwọn lọ si iforukọsilẹ ẹrú
26 ATER Auto-Tuning Error: Failed to perform Auto-Tuning function
  1. The PID values obtained after Auto-Tuning process are out of
    range. Retry Auto-Tuning.
    Auto-Tuning process exceeds 3600 secs
  2. Do not change the setpoint value during Auto-Tuning process.
  3. Use manual tuning instead of Auto-Tuning process.
  4.  Do not set the value as zero for TI & PB.
29 EEPR EEPROM ko le kọ bi o ti tọ Pada si olupese fun titunṣe.
30 CJER Biinu junction tutu fun

Thermocouple aiṣedeede

Pada si olupese fun titunṣe.
39 SBER Input sensor break Replace the input sensor
40 ADER Oluyipada A si D tabi awọn paati ti o ni ibatan Pada si olupese atilẹba fun atunṣe.

FAQ

Bawo ni MO ṣe wọle si Akojọ olumulo?

To access the User Menu, press the corresponding key on the controller.

Bawo ni MO ṣe mu Ipo-Tuning Aifọwọyi ṣiṣẹ?

To activate Auto-Tuning Mode, press and hold a specific key for 5 seconds.

How do I enter Manual Control Mode? To enter Manual Control Mode, press the designated key for 3 seconds. How do I perform calibration? To calibrate a parameter, press and hold the ENTER key for 5 seconds during the calibration procedure.

To enter Manual Control Mode, press the designated key for 3 seconds.

Bawo ni MO ṣe ṣe isọdiwọn?

To calibrate a parameter, press and hold the ENTER key for 5 seconds during the calibration procedure.